urement to determine the setting value (for example, with a high-precision measuring-voltage transformer). If
a primary correction is not necessary, retain the default setting.
i
i
NOTE
The
Magnitude correction
parameter has nothing to do with the internal adjustment of the input
circuit.
Power-System Data
5.4 Application and Setting Notes for Measuring Point Current 3-Phase (I-3ph)
SIPROTEC 5, Fault Recorder, Manual
115
C53000-G5040-C018-5, Edition 11.2017