Parameter Value
Description
yes
The positive gradient of the current in the positive-sequence system is
monitored.
no
The positive gradient of the current in the positive-sequence system is not
monitored.
The hysteresis is preset at the factory to 0.980 p.u. (equal to 2 %) of the parameter
dM/dt rise (/Filter
time)
and can be adjusted.
Parameter: dM/dt Drop Active - dM/dt Drop (/Filter Time) - dM/dt Drop Hysteresis - Filter Time
•
Default setting
(_:9841:104) dM/dt drop active
=
yes
•
Default setting
(_:9841:108) dM/dt drop (/Filter time)
=
0.300 A
•
Default setting
(_:9841:116) dM/dt drop hysteresis
=
0.980 p.u.
•
Default setting
(_:9841:112) Filter time
=
2 periods
With the
dM/dt drop active
parameter, you activate the gradient trigger in order to monitor the negative
gradients of the current in the positive-sequence system using the set filtering time (input in periods).
Parameter Value
Description
yes
The negative gradient of the current in the positive-sequence system is
monitored.
no
The negative gradient of the current in the positive-sequence system is not
monitored.
The hysteresis is preset at the factory to 0.980 p.u. (equal to 2 %) of the parameter
dM/dt drop (/Filter
time)
and can be adjusted.
Application and Setting Notes - I2 Trigger (Negative-Sequence System)
Parameter: Mode
•
Default setting
(_:9871:1) Mode
=
off
With the
Mode
parameter, you activate the trigger for normal operation (On) or for the test mode (Test).
Parameter Value
Description
on
The function block I2 Trigger is activated and the voltage in the negative-
sequence system is monitored on the basis of the set trigger parameter.
off
The function block I2 Trigger is deactivated.
test
The function block I2 Trigger is activated for test purposes.
Parameter: Max. Trigger Active/Max. Trigger/Max. Trigger Hysteresis
•
Default setting
(_:9871:101) Max. trigger active
=
yes
•
Default setting
(_:9871:105) Max. trigger
=
1.200 A
•
Default setting
(_:9871:113) Max. trigger hysteresis
=
0.980 p.u.
With the
Max. trigger active
parameter, you activate the level trigger in order to monitor the current in
the negative-sequence system and to prevent it from exceeding the set values.
Parameter Value
Description
yes
The current in the negative-sequence system is monitored for overcurrent.
no
The current in the negative-sequence system is not monitored for overcur-
rent.
The hysteresis is preset at the factory to 0.980 p.u. (equal to 2 %) of the parameter
Max. trigger
and can
be adjusted.
7.5.2.8
Fault Recorder
7.5 Trigger Functions 3-Phase
322
SIPROTEC 5, Fault Recorder, Manual
C53000-G5040-C018-5, Edition 11.2017
Summary of Contents for SIPROTEC 5
Page 8: ...8 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 18: ...18 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 134: ...134 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 212: ...212 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 422: ...422 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 426: ...426 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 452: ...452 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...
Page 490: ...490 SIPROTEC 5 Fault Recorder Manual C53000 G5040 C018 5 Edition 11 2017 ...