Access Control 
SiPass integrated 

Controller and Device Installation Guide 

MP 2.80 

 

 

 

A6V11164550 

 

Smart Infrastructure 

07.09.2020 

 

 

Summary of Contents for SiPass integrated

Page 1: ...Access Control SiPass integrated Controller and Device Installation Guide MP 2 80 A6V11164550 Smart Infrastructure 07 09 2020 ...

Page 2: ...tance of the document the recipient acknowledges these rights and undertakes not to publish the document nor the subject thereof in full or in part nor to make them available to any third party without our prior express written authorization nor to use it for any purpose other than for which it was delivered to him Edition 07 09 2020 Document ID A6V11164550 Siemens Switzerland Ltd 2020 ...

Page 3: ...ing USB Client Application 14 2 2 2 Network Discovery of AC5102 14 2 2 3 Configuring the AC5102 Port Mapper 14 2 2 4 RS232 mode on FLN 2 and FLN 3 15 2 2 5 Restoring Default Network and Password Settings 15 2 2 6 Recovering a Non responsive Board 16 2 2 7 ACC G2 Firmware Update Procedures 16 2 2 8 Restoring Updating Platform via SD Card 16 2 2 8 1 Preparing the SD Card 16 2 2 8 2 SD Card Upgrade P...

Page 4: ...3 Restoring Default Network and Password Settings 27 2 4 4 Recovering a Non responsive Board 28 2 4 5 Network Security 29 2 5 AC5100 ACC G1 30 2 5 1 Restoring Default Network and Password Settings 30 2 6 AC5200 ACC Lite 31 2 6 1 Restoring Default Network Password and PIN Settings 31 3 FLN Devices and Readers 32 3 1 ADD5100 Dual Reader Interface DRI 32 3 2 ADE5300 Eight Reader Interface ERI 32 3 3 ...

Page 5: ...o the USB PC port of the ACC unit 2 Insert the A plug end of the A B USB cable into the USB port of the host PC If the USB RNDIS driver is not available on the host PC already it will prompt you to install the same You can choose to install the USB RNDIS driver either from an Installation CD if available or from a specific location If you wish to install the driver from a specific location follow ...

Page 6: ...sword to start the Telnet session for configuring the ACC network parameters If you are using MP2 70 or later version of the ACC and the default or weak password is set you will be prompted to enter a new password before configuring the network settings If you are using MP2 70 SP1 or later version when you change the SIEMENS user password the password for the root user for a SSH connection will al...

Page 7: ...ules OPM Input Point Modules IPM Eight Input Output Module 8IO Intrusion Arming Terminals IAT 010 The ACC and FLN Service Tool can also assist in discovering Access Controllers in the local Ethernet segment and configuring the network parameters of these discovered controllers The Field Service Tool is designed to help you perform these tasks 1 2 1 Installation Run setup exe available under Tools ...

Page 8: ...n and the PC laptop is on the same physical Ether network as the ACCs that are to be discovered Click the Network Search button a list of not yet configured ACCs should appear Select one unit and examine its network settings If the tool is being run from the SiPass server select the correct network interface and then use the Copy As Host Copy Subnet and Copy Gateway settings If the tool is just be...

Page 9: ...the FLN Configuration Tool will show the device but it will be reported as Offline Latest Firmware can still be downloaded to this device after which selecting Refresh Display will show the device as online in the FLN Configuration Tool When this device is saved to the database using the Save New Device button the device will be reported as using the new Standard Communication If you do not upgrad...

Page 10: ...on on with the default password not the password entered during MP2 70 version installation If you then re install the MP2 70 build the new password that was set when MP2 70 was first installed will still be valid This also applies to login via the ACC G2 standalone USB configuration tool 1 3 2 User Security for ACC Lite LCD Keypad Menu These additional security measures were introduced in ACC ver...

Page 11: ...older is structured as follows Product Type ACC AP or ACC G2 ACC application image is stored at this level SD_Card This folder includes the SD Card platform image System_Update This folder includes the step by step downloadable images for each supported upgrade path From_Platform_v1 Step1 Step N From_Platform_vX Step Step M 2 1 1 Updating Controller Application via Firmware Download Note Current v...

Page 12: ...f current platform major version For example 2 17 5 means that the major version is 2 In the Firmware Release locate the folder named Controller Type System_Update From_Platform_v Major Version For example ACC G2 System_Update From_Platform_v2 Download images one by one by following the order of StepX sub folders If the StepX sub folders do not exist it means only single image must be downloaded N...

Page 13: ...n initiated ACC will reset after completion message will be displayed in the audit trail and the ACC will restart to initiate the platform upgrade During platform installation the controller is expected to reboot at least twice Database configuration and system settings will be kept Overall downtime is expected to be between 1 and 10 minutes depending on the size and fragmentation of database Reco...

Page 14: ...C and the IS ports is being used for connection to a Gateway service like a Sintony panel a Securitel Alarm dialler or is being used to connect to a HLI High level Lift Interface It is also possible to redirect logical FLN ports to different physical ports e g FLN 3b which does not exist on the AC5102 This is not normally needed since SiPass allows renumbering a FLN it will work after an initialis...

Page 15: ...on of the FLNs in AC5102 Technical Manual and follow as shown in the table below FLN2 FLN3 X600 X601 Each dip switch consists of two switches X602 X603 Each dip switch consists of two switches 2 2 5 Restoring Default Network and Password Settings The X992 jumper is near the battery for the Real Time Clock RTC Short the pins of X992 for 3 seconds using a jumper until the orange ERROR led is blinkin...

Page 16: ...rd by following the steps below 1 Insert the SD card into the computer 512MB minimum 2 GB maximum 512MB recommended for compatibility with older ACC revisions 2 Find compressed gz image in SD_Card folder Unzip to extract the wic file 3 Use Win32DiskImager in Tools ACC G2 SD Card Creator Tool folder to write the wic file to the SD Card Win32DiskImager defaults to open a file of extension type img s...

Page 17: ...mming has completed If the ACC G2 was manufactured before the year 2012 you might need to press the reset switch between the CPU and Ethernet connector to initiate the upgrade 3 Power down the ACC G2 and remove the SD Card and Jumper 4 Power up the ACC G2 and check if the new CCP2 platform has been installed 5 If the ACC G2 has not been upgraded repeat the SD Card Upgrade Procedure This may be nec...

Page 18: ... console for maintenance purposes and trouble shooting but in normal operation should be disabled so that it is not bound to the Ethernet interface but instead restricted to just the local USB Ethernet interface Note After the upgrade to CCP2 Platform SSH access is no longer available for end user Disable external access to the SSH server with the console command set ssh usb SSH access can be enab...

Page 19: ...ect to IPM OPM 8IO devices and Aperio AH30 Capacity for 500 000 cards Maximum 5 cards per user Large offline event buffer with up to 200 000 events Anti passback Linux O S Note Only Input Output devices and IAT are supported on the FLN Bus No RIM device support available The onboard Dual Reader Interface DRIe on the ACC AP can be programmed to function as any one of the door sets Dual Reader Two S...

Page 20: ... power monitoring IN 4 In 2 In case of ACC APM 12V 24V PSU Kit the pre wiring is already done for cabinet tamper RLY 1 Door 1 LK RLY 2 Out 1 OUT 1 Door 1 AUX OUT 2 Out 2 OUT 3 Out 3 OUT 4 Out 4 READER 1 Port for connecting both OSDP Readers READER 2 NOT USED 2 3 3 2 2 Single OSDP Reader Doors Configuration Label on AP Controller SiPass Point Function IN 1 Door 1 REX IN 2 Door 1 D C IN 3 Door 2 REX...

Page 21: ... is not compatible with ACC APM 12V 24V PSU Kit because IN 3 is pre wired for power monitoring and IN4 for cabinet tamper 2 3 3 4 OSDP Reader Turnstile Dual Door Contact Configuration Label on AP Controller SiPass Point Function IN 1 Door 1 REX IN 2 Door 1 D C IN 3 Door 2 REX IN 4 Door 2 D C RLY 1 Door 1 LK RLY 2 Door 2 LK OUT 1 Out 1 OUT 2 Out 2 OUT 3 Out 3 OUT 4 Out 4 READER 1 Port for connectin...

Page 22: ...es for Wiegand Reader 1 D1 A D0 B READER 2 Pins A and B of READER 2 port are the data lines for Wiegand Reader 2 D1 A D0 B 2 3 3 6 2 Single Wiegand Reader Doors Configuration Label on AP Controller SiPass Point Function IN 1 Door 1 REX IN 2 Door 1 D C IN 3 Door 2 REX IN 4 Door 2 D C RLY 1 Door 1 LK RLY 2 Door 2 LK OUT 1 Green LED for Reader 1 OUT 2 Red LED for Reader 1 OUT 3 Green LED for Reader 2...

Page 23: ... is not compatible with ACC APM 12V 24V PSU Kit because IN 3 is pre wired for power monitoring and IN4 for cabinet tamper 2 3 3 8 Wiegand Reader Turnstile Dual Door Contact Configuration Label on AP Controller SiPass Point Function IN 1 Door 1 REX IN 2 Door 1 D C IN 3 Door 2 REX IN 4 Door 2 D C RLY 1 Door 1 LK RLY 2 Door 2 LK OUT 1 Green LED for Reader 1 OUT 2 Red LED for Reader 1 OUT 3 Green LED ...

Page 24: ... document 2 3 5 Power Monitoring Limits The AP Controller should be provided with power in the range of 12V 24V DC The AP Power Supply must be protected by a fuse 2A An Audit Trail Message will be produced if the voltage level drops below 10 5V or goes above 26 5V Absolute maximum power ratings are 9 5V 29 5V DC The Reader Power Supply outputs are protected by a thermal fuse In the event of a shor...

Page 25: ...e the database configuration and system settings will be lost 1 Power down the controller and open the case to expose the circuit board 2 Insert the Micro SD Card in the slot as shown in the picture 3 While holding down the Factory Reset Button switch the unit on Release the button after 5 seconds The LED will show the following states as the controller is booting and updating RED The controller i...

Page 26: ... Common Firmware Update Procedure 11 section 2 3 9 LED Indications 2 3 9 1 During SD Card Update LED Indication Description RED On Siemens bootstrap and u boot running ORANGE Flashing NAND Flash update is in progress GREEN Flashing NAND Flash update finished SD card shutting down ORANGE On SD Card shut down Count to 7 remove power remove SD card restart After SD Card removal ACC Application runnin...

Page 27: ...rt the pins of X992 for 3 seconds using a jumper until the orange ERROR led is blinking quickly Remove the short and wait about 10 seconds for application to restart and reset the network settings The default network settings are IP Address 192 168 1 250 Subnet Mask 255 255 255 0 Default login credentials SIEMENS spirit All other settings are zeroed including the SiPass host address and modem conf...

Page 28: ...uld sometimes fail Make sure a file called boot bin is present in the top directory of the SD Card 3 Plug the SD card into the Controller while it is powered off 4 Place a jumper on Jumper X 120 and power up the Controller If the Controller was manufactured before 2012 Press the reset button once for at least a second and then release If the Controller was manufactured in 2012 or later the reset b...

Page 29: ... the SSH server listens on us 10022 This can be changed with the console command set ssh port xyz Where xyz is a valid and unique TCP port number The standard port number for SSH is port 22 but many network probing tools attack port 22 by default Root Password The username for gaining access to the linux shell is root the password is the default root password spirit The root password can be change...

Page 30: ... 250 Default ACC Subnet Mask 255 255 255 0 Once download is complete boot the ACC using the boot command in the HyperTerminal window Once the initial version of firmware has been downloaded new versions can be updated using SiPass integrated 2 5 1 Restoring Default Network and Password Settings The ACC G1 does not have a set defaults jumper It can be recovered as below 1 Downgrade to a 2 65 build ...

Page 31: ... and logging in for the first time with the default PIN will require setting a new PIN for security purpose The PIN must be secure with length from 4 10 digits Save this new PIN in a secure place after setting If you change the ACC Lite PIN but forget there is an ACC telnet Console command to change the PIN If both PIN and telnet passwords are lost then it must be returned to factory or Siemens If...

Page 32: ...ide for more Information 3 5 AFO5100 OPM The AFO5100 is programmed using FLN Configuration tool in SiPass integrated Configuration Client or using the stand alone ACC FLN Field Service Tool application See the appropriate User Guide for more Information 3 6 AFO5200 8IO The AFO5200 is programmed using FLN Configuration tool in SiPass integrated Configuration Client or using the stand alone ACC FLN ...

Page 33: ...ds are encoded with SiPass integrated More details can be found inside the training documentation 3 9 2 Required Settings for Reading the UID Number of a MIFARE Card 1 Open the FLN configuration and navigate to the RIM DRI ERI which the new ARxxx MF VRxxx MF reader is connected to 2 Download the new firmware to the corresponding RIM 3 Select ARxxx MF VRxxx MF OSDP reader technology in the Configur...

Page 34: ...tion dialog The following card technologies are supported CustomWiegand AllHidProx Prox26Bit ProxAsco36Bit ProxCorp1000 ProxSiemensEncr ProxSiemensStg MifareCsn32 MifareCsn40 WiegandBCD WiegandAscoFacility Indala27Bit Cotag27Bit Indala32Bit Prox36BitCodeCard Prox34BitCodeKey DigikeyProx NorwayPost MifareUID56 SaltoWiegand34 EricssonWiegand Europlex34Bit Remec37Bit See the documentation in SiPass i...

Page 35: ...mation Alternatively you can use the FLN Configurator and FLN Field Service Tool located in the Tools folder in SiPass integrated software bundle Features Up to 4 MFI devices per ACC AP can be connected with up to 4 doors per MFI total of up to 16 doors per ACC AP MFI I O Only Mode I O device with 8 inputs and 8 outputs Can be used for general I O intrusion and low level elevator control MFI Door ...

Page 36: ...orrect sectors and blocks from the cards This is especially required for existing site installations having various types of card technologies already in use Currently SiPass integrated supports the following card technologies in the FLN Configuration tool for Aperio Wireless Locks Siemens Mifare GID Siemens Mifare Facility Siemens RS485 UID All HID Prox Currently encoded on smart card only for Ap...

Page 37: ...Manual from the AH30 Hub manufacturer Assa Abloy for further details 3 13 Help and Documentation The hardware for Aperio Wireless Technology and Multi Function Interface MFI is not supplied by Siemens However to help you quickly setup everything SiPass integrated documentation gives you the required support information sourced from the device manufacturer The standard SiPass firmware documentation...

Page 38: ...erland Ltd Smart Infrastructure Global Headquarters Theilerstrasse 1a CH 6300 Zug 41 58 724 2424 www siemens com buildingtechnologies Siemens Switzerland Ltd 2020 Technical specifications and availability subject to change without notice ...