2.2.4
RS232 mode on FLN 2 and FLN 3
Using FLN 2 or FLN 3 in RS232 mode (for Securitel or Sintony integration) requires
that the EOL jumpers be set to OFF. This entails powering down the ACC-G2,
removing the FLN expansion module and then setting all the jumpers for the
appropriate ports to OFF.
A torx screwdriver bit of size T10 is required to remove the FLN expansion module.
A magnifying glass and a small screwdriver are useful for setting the EOL dip
switches.
See the
AC5102 Technical Manual
in the SiPass integrated software bundle for
more information.
Note: Disregard connections for FLN 2 & 3 sh
own in Section “Bus Termination of
the FLNs”
in
AC5102 Technical Manual
and follow as shown in the table below:
FLN2
FLN3
X600, X601
Each dip switch consists of two switches
X602, X603
Each dip switch consists of two switches
2.2.5
Restoring Default Network and Password Settings
The X992 jumper is near the battery for the Real Time Clock (RTC).
Short the pins of X992 for 3 seconds (using a jumper), until the orange ERROR led
is blinking quickly. Remove the short, and wait about 10 seconds for application to
restart and reset the network settings.
The default network settings are:
IP Address : 192.168.251.1
Subnet Mask : 255.255.255.0
Default Login Credentials:
SIEMENS/spirit
All other settings are zeroed, including the SiPass host address and modem
configuration is disabled. The Telnet server is re-enabled.
Use either Telnet, the USB Client Application or the Network Configurator tool to
restore the network settings.