7.7.2
Specific technical data, 690 V inverters
Table 7-31
PM240-2, IP20, frame size D, 500 V … 690 V 3 AC
Article No. - without filter
Article No. - with filter
6SL3210-1PH21-4UL0
6SL3210-1PH21-4AL0
6SL3210-1PH22-0UL0
6SL3210-1PH22 -0AL0
6SL3210-1PH22-3UL0
6SL3210-1PH22 -3AL0
LO base load power
11 kW
15 kW
18.5 kW
LO base load input current
14 A
18 A
22 A
LO base load output current
14 A
19 A
23 A
HO base load power
7.5 kW
11 kW
15 kW
HO base load input current
11 A
14 A
20 A
HO base load output current
11 A
14 A
19 A
Fuse according to IEC/UL
Fuse according to IEC/UL, Class J
3NA3807-6 (20 A)
20 A
3NA3810-6 (25 A)
25 A
3NA3812-6 (32 A)
30 A
Power loss without filter
0.35 kW
0.44 kW
0.52 kW
Power loss with filter
0.35 kW
0.45 kW
0.52 kW
Required cooling air flow
55 l/s
55 l/s
55 l/s
Weight without filter
17 kg
17 kg
17 kg
Weight with filter
18.5 kg
18.5 kg
18.5 kg
Table 7-32
PM240-2, IP20, frame size D, 500 V … 690 V 3 AC
Article No. - without filter
Article No. - with filter
6SL3210-1PH22-7UL0
6SL3210-1PH22-7AL0
6SL3210-1PH23-5UL0
6SL3210-1PH23 -5AL0
6SL3210-1PH24-2UL0
6SL3210-1PH24-2AL0
LO base load power
22 kW
30 kW
37 kW
LO base load input current
25 A
33 A
40 A
LO base load output current
27 A
35 A
42 A
HO base load power
18.5 kW
22 kW
30 kW
HO base load input current
24 A
28 A
36 A
HO base load output current
23 A
27 A
35 A
Siemens fuse according to IEC/UL
Fuse according to IEC/UL, Class J
3NA3817-6KJ (40 A)
35 A
3NA3820-6KJ (50 A)
45 A
33NA3822-6 (63 A)
60 A
Power loss without filter
0.60 kW
0.77 kW
0.93 kW
Power loss with filter
0.60 kW
0.78 kW
0.94 kW
Required cooling air flow
55 l/s
55 l/s
55 l/s
Weight without filter
17 kg
17 kg
17 kg
Weight with filter
18.5 kg
18.5 kg
18.5 kg