Table 7-12
PM240-2, IP20, frame size E, 200 V … 240 V 3 AC
Article No. without filter
6SL3210-1PC28-0UL0
6SL3210-1PC31-1UL0
LO base load power
22 kW
30 kW
LO base load input current
76 A
98 A
LO base load output current
80 A
104 A
HO base load power
18.5 kW
22 kW
HO base load input current
71 A
83 A
HO base load output current
68 A
80 A
Fuse according to IEC/UL
Fuse according to IEC/UL, Class J
3NA3830 (100 A)
100 A
3NA3836 (160 A)
150 A
Power loss
0.92 kW
1.28 kW
Required cooling air flow
83 l/s
83 l/s
Weight
26 kg
26 kg
Table 7-13
PM240-2, PT, frame size E, 200 V to 240 V 3 AC
Article No. without filter
6SL3211-1PC31-1UL0
LO base load power
30 kW
LO base load input current
98 A
LO base load output current
104 A
HO base load power
22 kW
HO base load input current
83 A
HO base load output current
80 A
Fuse according to IEC
Fuse according to UL, class J
3NA3836 (160 A)
150 A
Power loss
1.28 kW
1)
Required cooling air flow
83 l/s
Weight
29 kg
1)
approx. 1.1 kW through the heatsink
Technical data
7.5 Technical data, 200 V inverters
Power Module PM240-2
Hardware Installation Manual, 08/2017, A5E33294624B AG
87