Table 9-1
Technical data of the line reactors
Article number
Induc‐
tance
[mH]
Line/load connection
PE connection
Weight
[kg]
[mm
2
/ nM]
[AWG / lbf in]
[mm
2
/ lbf in]
6SL3203-0CE13-2AA0
2.5
2.5 / 0.8
14 / 7
M4 [3 / 26.5]
1.1
6SL3203-0CE21-0AA0
1
6 / 1.8
10 / 15.9
M4 [3 / 26.5]
2.1
6SL3203-0CE21-8AA0
0.5
6 / 1.8
10 / 15.9
M5 [5 / 44.3]
2.95
6SL3203-0CE23-8AA0
0.3
16 / 4
6 / 34.5
M5 [5 / 44.3]
7.80
The line reactors are designed to IP20 degree of protection.
Table 9-2
Assignment table
Line reactors
Power Module, 400 V
Power Module, 200 V
6SL3203-0CE13-2AA0
6SL3210-1PE11-8 . L1,
6SL3210-1PE12-3 . L1
6SL3210-1PE13-2 . L1
FSA
6SL3210-1PB13-0 . L0,
6SL321 . -1PB13-8 . L0
FSA
6SL3203-0CE21-0AA0
6SL3210-1PE14-3 . L1,
6SL321 . -1PE16-1 . L1
6SL321 . -1PE18-0 . L1
FSA
6SL3210-1PB15-5 . L0,
6SL3210-1PB17-4 . L0
6SL321 . -1PB21-0 . L0
FSB
6SL3203-0CE21-8AA0
6SL3210-1PE21-1 . L0,
6SL3210-1PE21-4 . L0
6SL321 . -1PE21-8 . L0
FSB
6SL3210-1PB21-4 . L0
6SL321 . -1PB21-8 . L0
FSC
6SL3203-0CE23-8AA0
6SL3210-1PE22-7 . L0,
6SL321 . -1PE23-3 . L0
FSC
6SL321 . -1PC22-2 . L0
6SL3210-1PC22-8 . L0
FSC
Line reactors for 1 AC 200 V
For inverters with 1 AC 200 V connection, rather than the line reactors listed above, you can
also deploy the following or similar products:
● FSA:
NKE 10 / 2.93 (Block company)
● FSB
NKE 25 / 1.17 (Block company)
● FSC
NKE 35 / 1.46 (Block company)
The technical properties and statements made by the manufacturer apply.