7.6.3
Current derating depending on the pulse frequency, 400 V inverters
Article number
LO
power
[kW]
LO base load output current [A]
Pulse frequency [kHz]
2
4
*)
6
8
10
12
14
16
6SL3210-1PE11-8 . L1
0.55
1.7
1.7
1.4
1.2
1
0.9
0.8
0.7
6SL3210-1PE12-3 . L1
0.75
2.2
2.2
1.9
1.5
1.3
1.1
1
0.9
6SL3211-1PE13-2 . L1
1.1
3.1
3.1
2.6
2.2
1.9
1.6
1.4
1.2
6SL3210-1PE14-3 . L1
1.5
4.1
4.1
3.5
2.9
2.5
2.1
1.8
1.6
6SL3210-1PE16-1 . L1
2.2
5.9
5.9
5
4.1
3.5
3
2.7
2.4
6SL321 . -1PE18-0 . L1
3
7.7
7.7
6.5
5.4
4.6
3.9
3.5
3.1
6SL3210-1PE21-1 . L0
4
10.2
10.2
8.7
7.1
6.1
5.1
4.6
4.1
6SL3210-1PE21-4 . L0
5.5
13.2
13.2
11.2
9.2
7.9
6.6
5.9
5.3
6SL321 . -1PE21-8 . L0
7.5
18
18
15.3
12.6
10.8
9
8.1
7.2
6SL3210-1PE22-7 . L0
11
26
26
22.1
18.2
15.6
13
11.7
10.4
6SL321 . -1PE23-3 . L0
15
32
32
27.2
22.4
19.2
16
14.4
12.8
6SL3210-1PE23-8 . L0
18.5
38
38
32.3
26.6
22.8
19
17.1
15.2
6SL3210-1PE24-5 . L0
22
45
45
38.3
31.5
27
22.5
20.3
18
6SL3210-1PE26-0 . L0
30
60
60
51
42
36
30
27
24
6SL321 . -1PE27-5 . L0
37
75
75
63.8
52.5
45
37.5
33.8
30
6SL3210-1PE28-8 . L0
45
90
90
76.5
63
54
45
40.5
36
6SL321 . -1PE31-1 . L0
55
110
110
93.5
77
---
---
---
---
Pulse frequency [kHz]
2
*)
4
6
8
10
12
14
16
6SL3210-1PE31-5 . L0
75
145
145
123.3 101.5
---
---
---
---
6SL3210-1PE31-8 . L0
90
178
178
151.3 124.6
---
---
---
---
6SL3210-1PE32-1 . L0
110
205
143.5
---
---
---
---
---
---
6SL321 . -1PE32-5 . L0
132
250
175
---
---
---
---
---
---
*) Factory setting
The permissible motor cable length depends on the particular cable type and the pulse frequency that
has been selected
Technical data
7.6 Technical data, 400 V inverters
Power Module PM240-2
100
Hardware Installation Manual, 08/2017, A5E33294624B AG