Table 7-10
PM240-2, IP20, frame size D, 200 V … 240 V 3 AC
Article No. without filter
6SL3210-1PC24-2UL0
6SL3210-1PC25-4UL0
6SL3210-1PC26-8UL0
LO base load power
11 kW
15 kW
18.5 kW
LO base load input current
40 A
51 A
64 A
LO base load output current
42 A
54 A
68 A
HO base load power
7.5 kW
11 kW
15 kW
HO base load input current
36 A
43 A
56 A
HO base load output current
35 A
42 A
54 A
Fuse according to IEC/UL
Fuse according to IEC/UL, Class J
3NA3822 (63 A)
60 A
3NA3824 (80 A)
70 A
3NA3830 (100 A)
90 A
Power loss
0.45 kW
0.61 kW
0.82 kW
Required cooling air flow
55 l/s
55 l/s
55 l/s
Weight
17 kg
17 kg
17 kg
Table 7-11
PM240-2, PT, Frame Size D, 200 V … 240 V 3 AC
Article No. without filter
6SL3211-1PC26-8UL0
LO base load power
18.5 kW
LO base load input current
64 A
LO base load output current
68 A
HO base load power
15 kW
HO base load input current
56 A
HO base load output current
54 A
Fuse according to IEC
Fuse according to UL, class J
3NA3830 (100 A)
90 A
Power loss
0.82 kW
1)
Required cooling air flow
55 l/s
Weight
19.5 kg
1)
approx. 0.72 kW through the heatsink
Technical data
7.5 Technical data, 200 V inverters
Power Module PM240-2
86