Application tips
5.5 Other application examples
TM15 / TM17 High Feature Operating Manual
Commissioning Manual, 05/2009
65
5.5.5
Multiple µs-granular measuring ranges
A maximum of one measuring range can be specified for the Measuring Input technology
object. Only measurements taken within this range are recorded.
The resolution of the measuring range of the Measuring Input technology object conforms to
the measuring input processing cycle clock (IPO interpolator cycle clock, IPO2 interpolator
cycle clock, or position control cycle clock).
If more than one measuring range is needed or if the measuring range is to be specified
more precisely, this can be accomplished in the application as described below:
●
Configure a Measuring Input technology object with level-triggered enable on the TM17
High Feature (measuring input e.g., DI/O 0; assigned enable input is therefore DI/O 10)
●
Configure an output cam track, and output this to an output of an output cam of TM17
High Feature. (Output of output cam e.g., to DI/O 12)
●
Connect the output of the output cam to the enable input of the measuring input
The output cam track is used to define the measuring range for the measuring input in the
application (each output cam corresponds to one measuring range and can therefore be
specified on a µs-specific basis).