Commissioning
7.6 Deleting data
SIMOTION C
158
Operating Instructions, 02/2012
7.6.4
Setting SIMOTION C to factory settings
Overview
SIMOTION C is supplied with preset parameters, such as the transmission rate or
PROFIBUS addresses. You can restore the factory settings with the mode selector. The
following data is deleted during this operation:
● "Non-volatile data" in the SIMOTION device
● The backup (PMEMORY.XML/PMEMORY.BAK) of the non-volatile data on the MMC
● User data in the "volatile data" and on the MMC
● The communication configuration (IP and DP parameters) is set to the factory settings
The licenses on the micro memory card are retained.
Operations on the mode selector
Proceed as follows:
1.
Switch off the power supply for SIMOTION C.
2.
The micro memory card is inserted in the SIMOTION C.
3.
Switch the mode selector to the MRES position. Keep this position selected and switch
the power supply for the SIMOTION C on. When the "STOPU" LED flickers, switch back
to the STOP position again.
Note
The communication configuration is now reset to the factory settings. The communication
configuration for the SIMOTION C must be repeated.