Functions
4.2 PGN parameters
SIMATIC PN/J1939 LINK
Operating Instructions, 12/2018, A5E45307564-AA
21
Parameter name Module name
Value range
Description
PGN data length PGN input n bytes
PGN output n bytes
8 to 512
PGN modules with specified data
lengths from 8 bytes to a maximum of
512 bytes are available.
If the value for the PGN data length
differs from the maximum module data
length, the difference in bytes is truncat-
ed from the PGN message.
Example:
You want to send 20 bytes of data. For
this purpose, you select a PGN output
module with a predefined size of 32
bytes. You specify 20 bytes as the PGN
data length.
Only these 20 bytes are transferred via
the CAN network. The remaining 12
bytes are truncated.
PGN input proxy
8 to 1785
Specification of the maximum PGN
message length. The corresponding
data must be read with the data record
index 0x220.
PGN output proxy
Specification of the maximum PGN
message length. The corresponding
data must be written with the data record
index 0x230.