Certification
6.2 EMC and Environmental Type Tests
EMC Immunity Type Tests for IEEE 1613
Note
The RUGGEDCOM RX1501 meets Class 2 requirements for an all-fiber
configuration and Class 1 requirements for copper ports. Class 1 allows for
temporary communication loss, while Class 2 requires error-free and interrupted
communications.
Description
Test Levels
Signal ports
5 kV (Failsafe Relay Output)
DC Power Ports
HV Impulse
AC Power Ports
5 kV
Signal ports
2 kV
DC Power Ports
1.5 kV
Dielectric Strength
AC Power Ports
2 kV
Signal ports
± 4 kV @ 2.5 kHz
DC Power Ports
AC Power Ports
Fast Transient
Earth ground ports
± 4 kV
Signal ports
2.5 kV common mode @1MHz
DC Power Ports
Oscillatory
AC Power Ports
2.5 kV common
1 kV differential mode @ 1 MHz
Radiated RFI
Enclosure ports
35 V/m
Enclosure Contact
± 8 kV
ESD
Enclosure Air
± 15 kV
Environmental Type Tests
Test
Description
Test Levels
Severity
Levels
IEC 60068-2-1
Cold Temperature
Test Ad
-40 °C (-40 °F), 16 Hours
IEC 60068-2-2
Dry Heat
Test Bd
85 °C (185 °F), 16 Hours
IEC 60068-2-30
Humidity (Damp
Heat, Cyclic)
Test Db
95% (non-condensing),
55 °C (131 °F), 6 cycles
IEC 60255-21-1
Vibration
2 g @ 10-150 Hz
Class 2
Shock
30 g @ 11 ms
Class 2
IEC 60255-21-2
Bump
10 g @ 16 ms
Class 1
Long Life (Random Vibration)
IEC 61373
Shock
Category 1 Class B
IEC 60255-21-3
Seismic
Method A
Level 2
RUGGEDCOM RX1501