Installing and connecting the device
3.3 Connecting the device
SIMATIC IPC847E
Operating Instructions, 10/2018, A5E43920357-AA
53
3.3.3.2
Connecting a redundant power supply (AC)
WARNING
Injury to persons or damage to property when operated on an incorrect power supply
system
If you connect the device to an unsuitable power supply, the device receives voltages and
currents that are too high or too low.
Injuries to persons, malfunctions or a damage to the device can result.
•
The permissible rated voltage of the device must match the local supply voltage.
•
Operate the device only in grounded power supply networks (TN networks in
accordance with VDE 0100 Part 100 or IEC 60364-1).
•
Operation in non-grounded or impedance-grounded networks is not permitted.
WARNING
Risk of electric shock
The on/off button and on/off switch do not fully disconnect the device from the mains.
There is also a risk of fire if the device or connecting lines are damaged.
•
Always fully disconnect the device from the mains voltage before performing work on
the device or when the device will not be used over an extended period of time.
•
For control cabinet mounting: Use a central, easily accessible AC circuit breaker close
to the device, if possible.