D-3
OP27, OP37 Equipment Manual
Release 05/99
Message
Cause
Remedy:
026...029
Storage medium not ready, contains errors or status unde-
finable.
Reset hardware, remove then refit Flash
memory module or carry out hardware test.
030
Storage medium not intialized.
Switch to download mode.
032
Error accessing module, Flash may not be supported or
initialized by incorrect OP.
Check whether module is properly inserted
and compatible.
If restoring: repeat backup with correct OP.
033
Internal Flash memory initialized; configuration data
deleted, some recipe data preserved.
Retransfer configuration.
034
Inserted module initialized, all stored data deleted.
Retransfer configuration.
035
Size of selected recipe memory has been reduced.
The reduced-size recipe memory can not
be used and all data records must be de-
leted. The recipe memory is only initialized
when requested.
040
Driver error
If FAP is set, the character delay time setting may be too
short.
Check physical connection with PLC.
Modify character delay time.
041
Fault in connection with PLC.
Possible causes:
–
Fault on the transmission link, e.g. connecting cable
defective
–
Incorrect interface parameters set on OP or on com-
munication peer.
043
Data transfer error. A variable indicating the cause of the
fault is transferred with this message.
Variable:
0
Timeout error
1
Framing error (receiving)
2
Overrun error
3
Parity error
4
No connection established
5
Checksum error (receiving)
6
Unexpected characters received
7...11
Internal error
12
Receive data block too large
13
Memory area not available on PLC
Repeat the data transfer. Before doing so,
check the physical connection/configured
interface parameters if necessary.
044
Fault in connection with PLC.
Possible causes:
–
Fault on the transmission link, e.g. connecting cable
defective
–
Incorrect interface parameters set on OP or on com-
munication peer.
114
PLC has been restarted.
115
Establishment of logical link with PLC in progress.
117
Connection with PLC is OK again following a fault.
119
Automatic restart.
136
PLC not responding.
Check program sequence on PLC. Check
physical connection.
138
Data block not available on PLC
Set up relevant memory area.
System Messages