D-9
OP27, OP37 Equipment Manual
Release 05/99
Remedy:
Cause
Message
565
On transferring a global data record, it is established that
not all entries are present.
You have the following options:
1: read the missing entries from the PLC
2: edit the missing entries
3: cancel the Download operation.
Only returned in the case of data records
that are transferable from one recipe to
another. rel. 3.0 or higher, plastic func-
tions.)
566
Data record contains array that does not fit the current
recipe structure.
The following question appears:
Save yes/no ?
If you elect to save, the array data is set to
0.
567, 568
If the message buffer has to be cleared, pending event/
alarm messages also have to be deleted in order to make
space for new message events.
Check configuration. Too many messages
are pending.
569
Fault on CPI module.
–
CPI no.: defective CPI module
–
Error:
1 = Voltage too low
2 = Current too high
3 = Temperature too high
4 = Module not present (failed during
operation)
571
S7 system diagnosis/ALARM_S returns error if OP logs
on/off.
CPU operating system out of date.
572
Query: data record already exists on data medium.
If 0 is entered the data record will be over-
written with the new values.
604
Message does not exist.
Configure message.
605
Process link is only configured symbolically.
Change configuration and retransfer.
606
Too many message variables configured.
g
g
607
Data type configured does not exist.
613
Data block not available or too short.
Create data block of required length on the
PLC.
622
Configured recipe does not fit in recipe mailbox on PLC
(> 512 data words).
Reduce configured size of recipe and re-
transfer configuration.
623
Internal error
Screen object for “Send Recipe“ is not a recipe type
(fixed by COM TEXT).
If the fault is not corrected by performing a
restart, please contact the SIMATIC Hot-
line.
624
No recipe entries found.
Set up area pointers and retransfer configu-
ration.
625
Recipe number does not exist.
Reconfigure recipe.
626
No setpoints have been configured.
g
p
627
Internal error
Configured keyboard block number too high.
Correct the block number.
628
Recipe does not fit in mailboxes.
Increase configured size of recipe mailbox
or succeeding recipe mailbox.