Configuring the device
5.19 Configure Sm@rt Server
Basic Panels 2nd Generation
66
Operating Instructions, 10/2016, A5E33293231-AB
5.19
Configure Sm@rt Server
Requirement
●
A Basic Panel with PROFINET interface and an HMI device image compatible with
WinCC (TIA Portal) V14 or higher.
●
The HMI device has a Sm@rt Server license that was transferred to the HMI device via
the Automation License Manager.
●
The HMI device has a project that was compiled with option
"Runtime settings > Services > Remote control > Start Sm@rtServer".
Procedure
1. Touch the "Internet Settings" icon.
2. Press the "Sm@rt Server" button.
3. Select "Start automatically after
booting" if the Sm@rtServer is to
be started together with the HMI
device instead of later with the
project.
Select "Close with Runtime" if
the Sm@rtServer is to be closed
together with the project.
4. Make sure that the "Accept
Socket connection" switch is in
the "ON" position. Otherwise, a
client connection to the
Sm@rtServer is not possible.
5. Assign secure passwords for
Password 1 and Password 2 for
access of the Sm@rtClients and
select the "View only" checkbox
if a Sm@rtClient is only permitted
to observe the HMI device with
this password. Always change
the default passwords.
6. Make other settings, if necessary, such as the ports. You can find additional information
on the settings in manual "WinCC Advanced > Visualize processes > Options >
WinCC Sm@rtServer > Basics > Settings for Sm@rt options > Configurations on the
HMI device > 'Sm@rtServer: Current User Properties' dialog".