A.2

Parameters, diagnostics messages and address space without PCS 

7

A.2.1

Parameter assignment

Parameter assignment in the user program

You can reconfigure individual channels of the module in RUN without this having an effect 

on the other channels.

Changing parameters in RUN

The parameters are transferred to the module with the "WRREC" instruction via data record 

128. 
The parameters set in STEP 7 are not changed in the CPU, which means that the parameters 

set in STEP 7 will be valid again after a restart of the CPU.
If you reconfigure a module and diagnostics are pending prior to the reconfiguration, these 

diagnostics are not signaled as "outgoing".

Output parameter STATUS of the WRREC

If errors occur when transferring parameters with the "WRREC" instruction, the module 

continues operation with the previous parameter assignment. The STATUS output parameter 

contains the corresponding error code. 
The STATUS output parameter is 4 bytes long and is configured as followed: 
● Byte1: Function_Num, general error code 
● Byte2: Error_Decode, location of the error code 
● Byte3: Error_Code_1, error code 
● Byte4: Error_Code_2, manufacturer-specific extension of the error code 
Module-specific errors are displayed via Error_Decode = 0x80 and Error_Code_1 / 

Error_Code_2. 

Error_ 

Code_1

Error_ 

Code_2

Cause

Remedy

0xB0

0x00

Number of the data record unknown

Enter valid number for data record.

0xB1

0x01

Length of the data record is incorrect

Enter valid value for data record length.

0xB2

0x00 to 0xFF Module cannot be reached

● Check station - is the module plugged in 

correctly?

● Check the parameters of the WRREC 

instruction.

0xE0

0x01

Wrong version in the header

Correct the version number of the parameter 

block.

Drivers, parameters, diagnostics messages and address space

A.2 Parameters, diagnostics messages and address space without PCS 7

Digital output module DQ 32x24VDC/0.5A HA (6DL1132-6BL00-0PH1)

Manual, 09/2018, A5E39265993-AA

31

Summary of Contents for SIMATIC ET 200SP HA DQ 32x24VDC/0.5A HA

Page 1: ...24VDC 0 5A HA 6DL1132 6BL00 0PH1 Manual 09 2018 A5E39265993 AA Security information 1 Preface 2 Product overview 3 Wiring 4 Parameters 5 Displays and interrupts 6 Technical specifications 7 Drivers parameters diagnostics messages and address space A ...

Page 2: ...l are those who based on their training and experience are capable of identifying risks and avoiding potential hazards when working with these products systems Proper use of Siemens products Note the following WARNING Siemens products may only be used for the applications described in the catalog and in the relevant technical documentation If products and components from other manufacturers are us...

Page 3: ...nel parameters 18 5 3 Explanation of the module channel parameters 19 6 Displays and interrupts 21 6 1 Status and error displays of the I O module DQ 32x24VDC 0 5A HA 21 6 2 Interrupts 24 7 Technical specifications 25 A Drivers parameters diagnostics messages and address space 29 A 1 Concept of the driver and diagnostics blocks 29 A 2 Parameters diagnostics messages and address space without PCS 7...

Page 4: ...Table of contents Digital output module DQ 32x24VDC 0 5A HA 6DL1132 6BL00 0PH1 4 Manual 09 2018 A5E39265993 AA ...

Page 5: ...with appropriate security measures e g use of firewalls and network segmentation in place Additionally Siemens guidance on appropriate security measures should be taken into account You can find more information about industrial security by visiting https www siemens com industrialsecurity Siemens products and solutions undergo continuous development to make them more secure Siemens strongly recom...

Page 6: ...Security information Digital output module DQ 32x24VDC 0 5A HA 6DL1132 6BL00 0PH1 6 Manual 09 2018 A5E39265993 AA ...

Page 7: ...uring the ET 200SP HA You can configure the following components of the ET 200SP HA when the following updates are installed Component of the ET 200SP HA Required updates DQ 32x24VDC 0 5A HA HSP0276 V02 00 00 Appendices The appendices provide information that is relevant for using the ET 200SP HA outside the PCS 7 environment Conventions Please also observe notes marked as follows Note A note cont...

Page 8: ...Preface Digital output module DQ 32x24VDC 0 5A HA 6DL1132 6BL00 0PH1 8 Manual 09 2018 A5E39265993 AA ...

Page 9: ... DQ 1 DQ 3 DQ 5 DQ c DQ 6 DQ 0 DQ 2 DQ 4 DQ 7 DQ 1 DQ 3 DQ 5 DQ d 0 1 2 3 4 5 6 7 DQ a 0 1 2 3 4 5 6 7 DQ b 0 1 2 3 4 5 6 7 DQ c 0 1 2 3 4 5 6 7 DQ d Module type and designation Output disable switch LED for diagnostics Module type color coding LED for maintenance Product version 2D matrix code Function status and firmware version Wiring diagram Color code for selection of the color coded labels L...

Page 10: ...utput disable switch If you want to pull the I O module in runtime you have to press the output disable switch for 3 seconds for the I O module to be deenergized When the output disable switch has been pressed for 3 seconds the LED DIAG flashes red the LED MT lights up yellow and the I O module generates a diagnostics message See section Status and error displays of the I O module DQ 32x24VDC 0 5A...

Page 11: ... distributor on the right side for connecting actuators to ground 6DL1193 6TP00 0BN0 dark terminal block with potential distributor on the right side for connecting actuators to ground The terminal block is not included in the scope of delivery of the I O module and must be ordered separately Note You can find additional information on the configuration in the system manual Digital output module D...

Page 12: ...26 28 30 DQ 6 DQ 0 DQ 2 DQ 4 DQ 7 DQ 1 DQ 3 DQ 5 DQ c DQ 6 DQ 0 DQ 2 DQ 4 DQ 7 DQ 1 DQ 3 DQ 5 DQ d Pin assignment on the front of the module 3 DQ a DQ 2 4 DQ a DQ 3 5 DQ a DQ 4 6 DQ a DQ 5 7 DQ a DQ 6 8 DQ a DQ 7 9 DQ b DQ 0 10 DQ b DQ 1 11 DQ b DQ 2 12 DQ b DQ 3 13 DQ b DQ 4 14 DQ b DQ 5 15 DQ b DQ 6 16 DQ b DQ 7 17 DQ c DQ 0 18 DQ c DQ 1 19 DQ c DQ 2 20 DQ c DQ 3 21 DQ c DQ 4 22 DQ c DQ 5 23 DQ ...

Page 13: ...not exceed 10 A overall Recommendation Use terminal blocks with potential distributors For the connection of actuators with 2 wires the following terminal block should be used Article No Function parameter 6DL1193 6TP00 0DN0 Allow new potential group light terminal block 6DL1193 6TP00 0BN0 Use potential group of the left module dark terminal block Connection of actuators with potential distributor...

Page 14: ...FWLRQ 7 63 DFNSODQH EXV LQWHUIDFH QIHHG PRGXOH VXSSO DW OLJKW WHUPLQDO EORFN 3RZHU EXV 7HUPLQDO EORFN DFNSODQH EXV LQ WKH FDUULHU PRGXOH 0 0 3 3 3 3 Figure 4 1 Block diagram DQ 32 24VDC 0 5A HA Wiring 4 3 Schematic circuit diagram Digital output module DQ 32x24VDC 0 5A HA 6DL1132 6BL00 0PH1 14 Manual 09 2018 A5E39265993 AA ...

Page 15: ...rgized To do this press the output disable switch for 3 seconds 2 You can recognize the output disable from the following responses DIAG LED flashes red MT LED lit yellow A diagnostics message was generated for the I O module Wiring 4 4 Pulling I O module in runtime output disable switch activated Digital output module DQ 32x24VDC 0 5A HA 6DL1132 6BL00 0PH1 Manual 09 2018 A5E39265993 AA 15 ...

Page 16: ...Wiring 4 4 Pulling I O module in runtime output disable switch activated Digital output module DQ 32x24VDC 0 5A HA 6DL1132 6BL00 0PH1 16 Manual 09 2018 A5E39265993 AA ...

Page 17: ...re the I O module with PCS 7 V9 0 or higher Parameters You define the functioning of the I O module via parameters See also Parameter assignment and structure of the module channel parameters Page 32 Digital output module DQ 32x24VDC 0 5A HA 6DL1132 6BL00 0PH1 Manual 09 2018 A5E39265993 AA 17 ...

Page 18: ... substitute value Shutdown Yes Channel Substitute value 1 0 1 0 Yes Channel Potential group Use potential group of the left module Allow new potential group Use potential group of the left module No Module Double wide terminal block 2 Enabled Disabled Disabled No Configuration HW Config 1 Only applicable when the value Output substitute value has been enabled for the Reaction to CPU STOP parameter...

Page 19: ...communication between the interface module and CPU Substitute value Only applicable when the value Output substitute value has been enabled for the Reaction to CPU STOP parameter The entered substitute value is output by the I O module in the following cases When there is no connection to the CPU for example PROFInet cable unplugged With CPU STOP Potential group A potential group consists of a gro...

Page 20: ...a server module in the station configuration Power supply of I O modules of a potential group All I O modules of a potential group have a shared power supply You can find additional information on the configuration of the potential group in the system manual SIMATIC Distributed I O System ET 200SP HA Double width terminal block I O module on terminal block with potential distributor Select the Dou...

Page 21: ... 12 13 DQ 4 14 DQ 7 DQ 1 DQ 3 DQ 5 DQ b 23 24 17 18 19 20 21 22 31 25 27 29 32 26 28 30 0 1 2 3 4 5 6 7 DQ a 0 1 2 3 4 5 6 7 DQ b 0 1 2 3 4 5 6 7 DQ c 0 1 2 3 4 5 6 7 DQ d DIAG LED green red MT LED yellow Channel status LED green PWR LED green Figure 6 1 LED displays Meaning of the LED displays The tables below explain the meaning of the status and error displays Remedial measures for diagnostics ...

Page 22: ...occurred Note After activating the output disable switch only the associated diagnostic alarm is pending Channel status LED The green LED channel status shows the signal level at the input terminal Table 6 3 Status display of the channel status LEDs LED channel status Meaning Off Process signal 0 or channel disabled Module has been switched off Module or channel diagnostics pending On Channel enab...

Page 23: ...LED Meaning Off Supply voltage L missing On Supply voltage L present Displays and interrupts 6 1 Status and error displays of the I O module DQ 32x24VDC 0 5A HA Digital output module DQ 32x24VDC 0 5A HA 6DL1132 6BL00 0PH1 Manual 09 2018 A5E39265993 AA 23 ...

Page 24: ...rt circuit to ground Retentive memory in carrier module defective Retentive memory in the terminal block defective Module is faulty Shutdown on button activation Maintenance messages The I O module generates a maintenance message for the following events Retentive memory in carrier module defective Retentive memory in the terminal block defective Displays and interrupts 6 2 Interrupts Digital outp...

Page 25: ...h energy saving function No PWM No Oversampling No Redundancy Redundancy capability No Supply voltage Rated value DC 24 V permissible range lower limit DC 19 2 V permissible range upper limit DC 28 8 V Reverse polarity protection Yes Input current Current consumption rated value 60 mA without load Current consumption max 70 mA without load Output voltage Rated value DC 24 V Power loss Power loss t...

Page 26: ...utput delay with resistive load 0 to 1 typ 54 µs 1 to 0 typ 48 µs Parallel switching of two outputs for uprating No for redundant control of a load Yes only outputs of the same group Switching frequency with resistive load max 100 Hz with inductive load max 2 Hz on lamp load max 10 Hz Total current of the outputs Current per channel max 0 5 A Current per module max 10 A Total current of the output...

Page 27: ...eparation Potential separation channels between the channels No between the channels and backplane bus Yes Isolation Isolation tested with 1 500 V DC 1 min type test Ambient conditions Ambient temperature during operation horizontal installation min 40 C horizontal installation max 70 C vertical installation min 40 C vertical installation max 60 C Dimensions Width 22 5 mm Height 115 mm Depth 138 m...

Page 28: ...n a temperature increase in the I O module The respective output switches on and off again cyclically clocked Note Cable length Ensure sufficient low resistance cable routing to the sensor actuators to reach the response threshold Depending on the cable cross section used there may be restrictions in the cable lengths that can be used Technical specifications Digital output module DQ 32x24VDC 0 5A...

Page 29: ...the PCS 7 library that implement the interface to the hardware including test functions These blocks perform two basic tasks They provide signals from the process to the AS for further processing They monitor modules IO devices and IO controllers for failure When the process signals are read in these blocks access the process image input or process image partition PII and when the process signals ...

Page 30: ...cify the version of the driver library from which the driver blocks are to be imported in the Generate module drivers dialog box Time optimized processing For time optimized processing of the user program in runtime PCS 7 automatically carries out the following programming tasks Divide organization blocks for error handling for example OB 85 OB 86 into runtime groups Installing driver blocks in th...

Page 31: ...arameter contains the corresponding error code The STATUS output parameter is 4 bytes long and is configured as followed Byte1 Function_Num general error code Byte2 Error_Decode location of the error code Byte3 Error_Code_1 error code Byte4 Error_Code_2 manufacturer specific extension of the error code Module specific errors are displayed via Error_Decode 0x80 and Error_Code_1 Error_Code_2 Error_ ...

Page 32: ...ameters Structure of data record 128 Data record 128 has a length of 76 bytes It contains the channel parameters of the 32 channels HDGHU LQIRUPDWLRQ PRGXOH KDQQHO LJLWDO RXWSXW KDQQHO KDQQHO KDQQHO KDQQHO WH HDGHU LQIRUPDWLRQ FKDQQHO WH 0RGXOH SDUDPHWHUV WH WH WH WH WH WH LJLWDO RXWSXW LJLWDO RXWSXW LJLWDO RXWSXW LJLWDO RXWSXW Figure A 1 Structure of data record 128 Drivers parameters diagnostics...

Page 33: ... WH WH 1XPEHU RI VXEVHTXHQW FKDQQHO SDUDPHWHU EORFNV HQJWK RI WKH FKDQQHO SDUDPHWHU EORFN E WHV 5HVHUYHG 5HVHUYHG 5HVHUYHG 5HVHUYHG 5HVHUYHG WH WH WH Figure A 2 Header information and module parameters of data record 128 Channel parameters Each channel parameter block contains the channel parameters for a digital output 2 bytes Drivers parameters diagnostics messages and address space A 2 Paramete...

Page 34: ...read in the diagnostics buffer of the CPU Diagnostic messages are assigned either channel specific to an output or assigned as module messages to all outputs All channels are switched off for diagnostics messages that affect the entire module Only the corresponding digital output is affected by diagnostics messages which refer to individual channels Table A 1 Diagnostics messages their meanings an...

Page 35: ... events A maintenance event is generated for each maintenance required identified The MT LED lights up on the module Maintenance messages have no direct effect on the function of the module or digital outputs Table A 2 Maintenance messages their meaning and possible remedies Maintenance message Error code Assign ment Meaning Cause Remedy Retentive mem ory in carrier module defective 154H Module Fa...

Page 36: ...atus There is a bit value status for each digital output in the input address space Irrespective of the diagnostics enables each value status provides information on the validity of the corresponding process value Value status 1 Process value okay good Value status 0 Process value not okay bad Basically the value status is set to good if the digital value can be output without error The value stat...

Page 37: ...ns 10 Module parameters 18 Parameter Parameters 18 Pin assignment 12 13 Potential distributor 13 Properties 10 Schematic circuit diagram 14 Technical specifications 25 L LED displays 21 M Module parameters 18 MT LED 22 P Parameters 17 18 Pin assignment 12 13 Potential distributor 13 PWR LED 23 S Schematic circuit diagram 14 T Technology parameters 32 Terminal block 10 13 V Value status Evaluating ...

Page 38: ...Index Digital output module DQ 32x24VDC 0 5A HA 6DL1132 6BL00 0PH1 38 Manual 09 2018 A5E39265993 AA ...

Reviews: