Properties
The I/O module has the following technical properties:
● 32 digital outputs with the following properties that can be individually configured for each
channel
– Diagnostics
– Substitute values
● Source output (PNP, switching to P potential)
● Module-specific configurable diagnostics for missing supply voltage L+
● Output current (Total current of all channels: Max. 10 A; single channel: Max. 0.5 A)
● Suitable for solenoid valves, DC contactors, and indicator lights
The I/O module supports the following functions:
● Firmware update
● I&M identification data
● Parameter reassignment in RUN
● Value status QI
You can configure the I/O module with HW Config and integrate it into your system.
Output disable switch
If you want to pull the I/O module in runtime, you have to press the output disable switch for
3 seconds for the I/O module to be deenergized.
When the output disable switch has been pressed for 3 seconds, the LED DIAG flashes red,
the LED MT lights up yellow and the I/O module generates a diagnostics message. See section
Status and error displays of the I/O module DQ 32x24VDC/0.5A HA (Page 21).
Note
Pressing the output disable switch interrupts any ongoing firmware update. A firmware update
cannot be performed when the device is deenergized.
Accessories
The following accessories must be ordered separately:
● Labeling strips
● Color-coded labels
● Reference identification label
● Shield connector
Product overview
3.1 Properties of the I/O module DQ 32x24VDC/0.5A HA
Digital output module DQ 32x24VDC/0.5A HA (6DL1132-6BL00-0PH1)
10
Manual, 09/2018, A5E39265993-AA