Pulling I/O module in runtime / output disable switch activated
Pulling I/O module in runtime
If the I/O module is to be plugged in runtime, note the following:
1. The I/O module must be deenergized.
To do this, press the output disable switch for 3 seconds.
2. You can recognize the output disable from the following responses:
– DIAG LED flashes red, MT LED lit yellow
– A diagnostics message was generated for the I/O module.
Wiring
4.4 Pulling I/O module in runtime / output disable switch activated
Digital output module DQ 32x24VDC/0.5A HA (6DL1132-6BL00-0PH1)
Manual, 09/2018, A5E39265993-AA