A.1 Acceptance Log
ET 200pro FC
Operating Instructions, 07/2016, A5E01100763B AC
167
Function test "Safe Torque Off" (STO)
This test comprises the following steps:
Table A- 4
"Safe Torque Off" function (STO)
No.
Description
Status
1.
Initial state
•
Drive is "Ready to Run" (P0010 = 0)
•
No safety faults and alarms
•
r9772.0 = r9772.1 = 0 (STO de-selected and inactive)
•
P9659 = time intervals for the forced checking procedure correctly set
2.
Operate the drive
3.
Check that the expected drive operates
4.
Select STO while issuing the command to operate
5.
Check the following:
•
The drive coasts-down
•
The drive is braked by the mechanical brake and held if a brake is being
used
•
No safety faults
•
r9772.0 = r9772.1 = 1 (STO selected and active), r9772.14 = 1 if Safe
Brake Control is enabled
6.
De-select STO
7.
Check the following:
•
No safety faults
•
r9772.0 = r9772.1 = 0 (STO de-selected and inactive) , r9772.14 = 0
8.
Check that the expected drive operates if so the following is tested:
•
That the wiring between the control unit and power module is correct
•
Correct assignment, drive No. – inverter power module – motor
•
That the hardware is correctly functioning
•
That the shutdown paths have been correctly wired
•
Correct assignment of the STO terminals on the control unit
•
Correct parameterization of the STO function
•
Routine for the forced checking procedure of the shutdown paths
Summary of Contents for Simatic ET 200pro FC
Page 1: ......
Page 2: ......
Page 12: ...Table of contents ET 200pro FC 12 Operating Instructions 07 2016 A5E01100763B AC ...
Page 180: ...Appendix A 3 Standards ET 200pro FC 180 Operating Instructions 07 2016 A5E01100763B AC ...
Page 192: ...Glossary ET 200pro FC 192 Operating Instructions 07 2016 A5E01100763B AC ...
Page 195: ......
Page 196: ......