Commissioning and optimization (software)
7.4 Commissioning of communication between the S7 CPU and the frequency converter
ET 200pro FC
110
Operating Instructions, 07/2016, A5E01100763B AC
Properties of the parameter channel
●
One 16-bit address for each parameter number and subindex.
●
Transfer of different parameters in one access (multiple request).
●
Entire fields or parts of fields can be transferred.
●
Only one parameter request is processed at a time (no pipelining).
●
A parameter request/response must fit into a data set (on PROFIBUS: max. 240 bytes).
●
The header of the task or the response are user data.
●
Only 1 master or 1 supervisor on a frequency converter can be cyclically accessed at a
time.
Structure of parameter request and parameter response
Each parameter request consists of three parts:
Request header:
ID for the request and number of parameters being accessed.
Parameter address:
Addressing a parameter. If multiple parameters are being accessed there will be a
corresponding number of parameter addresses. The parameter address appears in the
request and not in the response.
Parameter value:
For each parameter addressed there is a segment for the parameter values. Depending on
the request ID, the parameter values appear either only in the request or in the response.
Summary of Contents for Simatic ET 200pro FC
Page 1: ......
Page 2: ......
Page 12: ...Table of contents ET 200pro FC 12 Operating Instructions 07 2016 A5E01100763B AC ...
Page 180: ...Appendix A 3 Standards ET 200pro FC 180 Operating Instructions 07 2016 A5E01100763B AC ...
Page 192: ...Glossary ET 200pro FC 192 Operating Instructions 07 2016 A5E01100763B AC ...
Page 195: ......
Page 196: ......