Commissioning and optimization (software)
7.6 Performing a reset to factory settings
ET 200pro FC
Operating Instructions, 07/2016, A5E01100763B AC
127
7.6.1
Factory settings
Factory default settings
After the frequency converter is reset to the factory settings, it can be operated without any
additional parameterization provided the default settings of the frequency converter match
the following data of a 4-pole motor:
Default line frequency
50 Hz
Rated motor voltage
P0304
Rated motor current
P0305
Rated motor output
P0307
Rated motor frequency
P0310
Rated speed
P0311
(We recommend a Siemens standard motor.)
The following conditions must also be fulfilled:
Control (ON/OFF command) through fieldbus
P0700=6
Asynchronous motor
P0300=1
Self-cooled motor
P0335=0
Motor overload factor
P0640=150 %
Setpoint input through fieldbus
P1000=6
Minimum frequency
P1080=0 Hz
Maximum frequency
P1082=50 Hz
Ramp-up time
P1120=10 s
Ramp-down time
P1121=10 s
Linear V/f characteristic
P1300=0
Note
If the settings made go beyond the factory settings, then careful attention must be paid -
depending on the complexity of the application - to the description of special functions and to
the parameter list plus function diagrams when commissioning the frequency converter.
Summary of Contents for Simatic ET 200pro FC
Page 1: ......
Page 2: ......
Page 12: ...Table of contents ET 200pro FC 12 Operating Instructions 07 2016 A5E01100763B AC ...
Page 180: ...Appendix A 3 Standards ET 200pro FC 180 Operating Instructions 07 2016 A5E01100763B AC ...
Page 192: ...Glossary ET 200pro FC 192 Operating Instructions 07 2016 A5E01100763B AC ...
Page 195: ......
Page 196: ......