Getting Started
Windows Automation Center, WinAC Slot Version 4.0
54
Hardware Installation and Operating Manual, Edition 02/2006, A5E00273194-02
Opening the Station Configuration Editor
To assign the name to the PC station, open the Station Configuration Editor by
clicking the
symbol in the toolbar.
Information on the Station Configuration Editor
For more information, e.g., on diagnostics in the Station Configuration Editor, refer
to the relevant online help.
3.4 Commissioning
3.4.1 Recommended
Procedure for Commissioning
Commissioning a PC with CPU 41x-2 PCI
To commission a PC with a CPU 41x-2, we recommend the following procedure:
1. Check again to make sure that the CPU 41x-2 PCI has been properly installed
and parameterized (see checklist in Checks Before Initial Turn-On of the PC
with CPU 41x-2 PCI) and that the WinAC Slot software package has been
properly installed.
2. Disconnect any DP line that is connected.
3. Turn on the PC.
4. Access the controller panel:
Start > Simatic > PC Based Control > CPU 412-2 PCI V4or
Start > Simatic > PC Based Control > CPU 416-2 PCI V4
Note
It is assumed in the following that you have saved the CPU 41x-2 PCI in the
Station Configuration Editor under the name "CPU 412-2 PCI" or "CPU
416-2 PCI".
5. The following LEDs light up on the controller panel:
- Green ON display
- Yellow STOP display
Check the backup battery and the position of the DIP Switch S1 on Switch
Block S2 for suppression of battery monitoring if the red BATF display is lit as
well.
More up-to-date information about the controller panel, when available, is
provided in the Readme file. You can access this Readme file in the following
directory:
Start > Simatic > Product Info > English