Reference Information
Windows Automation Center, WinAC Slot Version 4.0
Hardware Installation and Operating Manual, Edition 02/2006, A5E00273194-02
123
Pulse-Shaped Interferences
The following table presents the electromagnetic compatibility of modules with
respect to pulse-shaped interferences. This presupposes that the system complies
with the specifications and guidelines on electrical installation.
Pulse-Shaped Interference
Tested with
Correspond-
ing Severity
Electrostatic discharge in
accordance with
IEC 61000-4-2
Air discharge: ± 8 kV
Contact discharge: ± 6 kV
3
Burst pulses in accordance with
IEC 61000-4-4
2 kV
3
High-energy surge in
accordance with IEC 61000-4-5
•
Asymmetrical interference
•
Symmetrical interference
2 kV (supply line) DC voltage with
protectors
2 kV (data line)
1 kV (supply line) DC voltage with
protectors
3
Sinusoidal Interferences
The following table presents the EMC behavior with respect to sinusoidal
interferences:
Sinusoidal
Interference
Tested with
Corresponding
Severity
HF radiation
(electromagnetic fields)
in accordance with IEC
61000-4-3
10 V/m with 80% amplitude
modulation of 1 kHz over the range
of 80 MHz to 1000 MHz and 1,4 GHz
to 2 GHz
3
Conducted RF
interference on cables
and cable shields in
accordance with IEC
61000-4-6
Test voltage of 10 V with 80%
amplitude modulation of 1 kHz over
the range of 10 KHz to 80 MHz
3
Emission of Radio Interferences
Radio interference in accordance with EN 55022: Limit Class B.
Performing Work on the Prod
To protect the product from discharge of static electricity, operating personnel must
take appropriate action to discharge static electricity from their bodies prior to
touching the module.