User Tasks
2.1 Creating and configuring the STEP 7 Project
Microbox 427B-RTX/ -HMI/RTX and Panel PC 477B-HMI/ -HMI/RTX
Manual, 12/2007, A5E01217837-01
35
Microbox 427B-RTX/ -HMI/RTX or Panel PC 477B-HMI/RTX product. The default IP address
is 192.168.1.2 and the default subnet mask is 255.255.255.0. If you use a different IP
address, subnet mask, or if you use a gateway, configure these values in both the Windows
network configuration and in STEP 7. See the topic " Configuring the Windows Ethernet
Interface (Page 37) " for more information.
Creating programs for WinLC RTX (WinAC RTX)
In the SIMATIC Manager, you create the PLC programs for WinLC RTX in the same way
that you create PLC programs for any other SIMATIC controller.
Downloading the program and configuration
Next, you download the program and configuration. Check the following conditions before
you download:
Table 2-1
Required Conditions for Program and Configuration Download
Download Task
Required Conditions
Complete the download of the PC Station
Make sure that the Enhanced Write filter is in the
"Disabled" state. See the topic " Downloading PC
Station Components " for details.
Download PLC Program of WinLC RTX only
With the standard configuration, you can download
the PLC program at any time.
Download configuration data of WinLC RTX
and the CP 5611
With the standard configuration, you can download
the configuration data of WinAC RTX at any time.
If some of the configuration data may affect
configuration information of the complete PC Station
(such as changing address and bus settings of the
PROFIBUS interface associated with WinAC RTX),
perform a complete download of the PC Station.
Download Configuration data for the OPC
Server or IE_General
The download is only possible if the Write filter is in
the "Disabled" state. See the topic " Downloading
PC Station Components " for details.
Finalizing your SIMATIC Embedded PC for operation
To finalize your Microbox 427B-RTX/ -HMI/RTX or Panel PC 477B-HMI/RTX for operation,
the following steps are recommended:
●
Set the Enhanced Write Filter to the "Enabled" state for the C:\ drive. See the topic
"Managing the Enhanced Write Filter" for details.
●
Document any special settings (for example, changes to the IP address) for the
Embedded Bundle, which you made through your application development. Store them
together with your STEP 7 or WinCC flexible project.
NOTICE
Leaving the Enhanced Write Filter in the default "Disabled" state may lead to an early
failure of the CompactFlash card, due to ongoing write access of the operating system.
See the topic "Managing the Enhanced Write Filter" for details.