SIJECT OP15B Screens
SIJECT 16i Operation Manual
3-32
Secondly, select valve type, such as pressure valve; then select valve limit,
such as maximum:
Choose “Max.” in valve limit, and change its value by softkey:
1. Use cursor key
or
to enter valve adjustment selection;
2.
Press selection key
, and cursor moves to left;
3. Use cursor key
or
to select “Max.”;
4. Confirm it with Enter Key;
5. Press softkey F3 “
” to increase the “Max.”; or use softkey F4“-” to
reduce “Max.”. This process can be observed by external
amperemeter.
After finishing the adjustment of the valves. Select OFF to stop valve
adjustment.
Lastly, check the adjustment result:
In the “Force Output” mode, implement the “Pressure Test”:
1. Press softkey F2 “Force Output”, and the upper box will backlight;
2. Set the value of 140bar in Pressure Test;
3. Check if the external amperemeter reaches the maximum, such as
1Amp.