Appendices
A.1 Structure of user data/process data
ATD4xxW Door Controller for Industrial Applications
294
System Manual, 01/2017, A5E38080677-AB
DPOS signal
The DPOS signal is located in the high byte of TZW1 (bits 9 to 15). It has an enumerative
structure and is assigned the current door position (DPOS) in %.
Table A- 28 DPOS signal
DPOS signal
value
Name
Description
0 … 100
Door position
Door position in %
Note: The value is only valid in normal mode
The 100 % and 0 % door positions can only be reached in
conjunction with the "open" or "close" drive orders.
The 99 % and 1 % door positions correspond to fully open or
fully closed without an active drive order.
Values between 99 % and 1 % specify the door position as a
percentage value.
127 or 7F
hex
is sent (>100 %) if no valid position value is
available.
In partial opening mode, the door position continues to be
referred to the real door width. The values 100 and 99 % are
not reached in partial opening mode.