2.2 The five safety rules for electrical work
NFPA 70E “Standard for Electrical Safety in the Workplace” prescribes safety rules for working in
and on electrical
systems. To ensure the safety of persons and property in accordance with the standards, always comply with the
following safety rules:
Securing an electrical system before starting work
Before starting work on and in electrical installations, apply the following five safety rules:
1. Disconnect the charging station from the voltage source
2. Secure against reclosing
3.
Ensure
there
is
no
voltage
present
4. Install temporary grounding means
5. Install temporary shields over any adjacent live parts
Prepare to switch on again after work is finished
After finishing and checking the work, prepare the restart as follows:
• Inform persons no longer required that the work is completed and no further work is
permitted.
•
Withdraw
all
persons
no
longer
required.
• Remove all tools, equipment, and aids used.
Switch on the electrical system again
After finishing the work, remove the protective measures and switch the system on again:
1. Remove temporary shields over live parts
2. Remove temporary grounding means
3. Reinstate any reclosing
4. Close and latch all doors
5. Switch the system back on