Troubleshooting
1)
Safety feature!
This remedy action amounts to a reversal (disabling) of a safety pre-
caution installed earlier. Please do ensure that such disabling is now
permissible / authorized!
Fixed-mounted
circuit- breaker
Draw-out
circuit breaker
Disturbance
Cause
Remedy
X
X
circuit breaker cannot be
closed and circuit breaker
not
ready to close.
Ready-to-close indicator
shows:
1. Spring not charged
Charge spring
X
X
2. Undervoltage release not
energized
Energize undervoltage release
X
X
3. Mechanical reclosing lock-out
effective
Rectify cause of overcurrent trip-
ping and press reset button
X
X
4. Electrical closing interlock
effective
Switch off control voltage for inter-
locking
1)
X
X
5. “OFF” locked off by cylinder
lock (accessories)
Unlock
1)
X
X
6. “OFF” locked off by
padlocks
(accessories)
Remove padlocks
1)
X
X
7. “Mechanical OFF” button
locked off (accessories)
Unlock the “Mechanical OFF”
button
1)
X
X
8. “EMERGENCY OFF” button
engaged in operating position
(accessories)
Release “EMERGENCY OFF”
button
1)
by rotating it
X
X
9. Lockout against closing with
cubicle door open effective
(accessories)
Close cubicle door
X
X
10. Mutual mechanical circuit
breaker interlocks effective
(accessories)
Open second circuit breaker or rack
into disconnected
position
1)
X
X
11. Electronic overcurrent release
(trip unit) missing or incorrectly
installed
Fit electronic overcurrent release
properly
X
X
12. Shunt trip energized
De-energize shunt trip
X
X
13. Closing coil energized
Closing coil has to be de-energized
shortly for reclosing
X
14. Racking handle withdrawn
Rack circuit breaker into discon-
nected, test or connected position,
unlatch crank and push it fully in
discharged
CHARGED
6.9
Störungsbeseitigung
→
Summary of Contents for Sentron WL
Page 15: ...3ZX1812 0WL00 0AN4 0 XV ...
Page 77: ...3ZX1812 0WL00 0AN4 7 14 ...
Page 100: ...9 15 3ZX1812 0WL00 0AN4 S Auslösung I Auslösung S tripping I tripping ...
Page 101: ...3ZX1812 0WL00 0AN4 9 16 Erdschlussauslösung Ground fault tripping ...
Page 130: ...9 45 3ZX1812 0WL00 0AN4 ...
Page 249: ...3ZX1812 0WL00 0AN4 14 4 ...