Alarm, error, and system messages
7.1 Description of the alarms on the SPP2000
PROFINET Proxy SPP2000
68
Equipment Manual, 03/2022, L1V30814715D-01
"UserStructureIdentifier" data block
Bits
Meaning
0x0000 … 0x7FFF
User-specified
0x8000
ChannelDiagnosis
0x8002
Extended ChannelDiagnosis
The SPP2000 signals all diagnostic interrupts as "ChannelDiagnostic Alarms". For that reason,
the value of the "UserStructureIdentifier" field for the diagnostic interrupt is always "0x8000".
The hardware interrupts are signaled as "User specified" and have a value from 1 to XXX. The
precise structure of the hardware interrupts is described below.
"ChannelNumber" data block
For diagnostic interrupts only.
ChannelNumber
Meaning
0x0000 … 0x7FFF
Manufacturer-specific
0x8000
Submodule
"ChannelProperties" data block
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
.Direction
.Specifier
.Qualifier .Acc.
.Type
"ChannelProperties.Type (bits 0 to 7)" data block
Value
Meaning
0
If ChannelNumber has the value 0x8000.
1
1 bit
2
2 bits
3
4 bits
4
8 bits
5
16 bits
6
32 bits
7
64 bits
"ChannelProperties.Accumulative (Bit 8)" data block
Value
Meaning
0
No channel error group signal
1
Channel error group signal (more than one channel affected)