Data traffic
6.2 Cyclic data traffic
PROFINET Proxy SPP2000
Equipment Manual, 03/2022, L1V30814715D-01
35
6.2.2
Basic type 1
Structure
The structure of basic type 1 is fixed. The length of basic type 1 is 20 bytes of input data and
2 control bytes (output data). The following information is transferred in basic type 1.
Table 6- 1
Structure of basic type 1
Byte
Data value
Format
Unit
0 ... 3
Status information
Unsigned long
—
4 ... 7
Current L1
Float
A
8 ... 11
Current L2
Float
A
12 ... 15
Current L3
Float
A
16 ... 19
Total active power
Float
W
6.2.3
Basic type 2
Structure
The structure of basic type 2 is fixed. Basic type 2 is 24 bytes long.
Basic type 2 is an extension of basic type 1. This means that you can easily add basic type 1
and basic type 2 during the project design phase. You can also use basic type 2 as a separate
unit.
Table 6- 2
Basic type 2 transfers the following input data
Byte
Data value
Format
Unit
0 ... 3
Voltage L1-L2
Float
V
4 ... 7
Voltage L2-L3
Float
V
8 ... 11
Voltage L3-L1
Float
V
12 ... 19
Active energy import tariff 1
Double
Wh
20 ... 23
Total power factor
Float
—