Data traffic
6.3 Acyclic data traffic
PROFINET Proxy SPP2000
52
Equipment Manual, 03/2022, L1V30814715D-01
6.3.8
DS131 PAC device parameters
Via data set DS131, the parameterization of the limits of the individual PAC device can be
read and modified.
This data set only applies to the SENTRON PAC devices. The corresponding slot/subslot
address must therefore be used for reading.
Table 6- 12 Structure of data set DS131 - read access and write access
Byte
Length
(bits)
Format
Description
PAC2200
PAC2200
MID
PAC2200
CLP
PAC3200T
0
32
Unsigned16
Rated current display
range
R/W
R/W
R/W
4
32
Unsigned long Connection type
R/W
R/W
R/W
R/W
8
32
Unsigned long Voltage transformer
(1=yes; 0=no)
R/W
12
32
Unsigned long Primary voltage
R/W
16
32
Unsigned long Secondary voltage
R/W
20
32
Unsigned long Primary current
R/W
R/W
R/W
R/W
24
32
Unsigned long Secondary current
R/W
R/W
R/W
R/W
28
32
Float
Zero point suppression
R/W
32
32
Unsigned long Load profile demand
period
R/W
R/W
R
R/W
36
32
Unsigned long Synchronization via bus
R/W
R/W
R
R/W
40
32
Unsigned long DI types of use
R/W
R/W
R/W
R/W
44
32
Unsigned long Input transition vs. pulse
R/W
48
32
Unsigned long Input type index
R/W
R/W
R/W
R/W
52
32
Unsigned long Input pulse ratio (pulses
per kWh/kvarh)
R/W
R/W
R/W
R/W
56
32
Unsigned long Group assignment of
digital output
R/W
R/W
R/W
R/W
60
32
Unsigned long Digital output action
R/W
R/W
R/W
R/W
64
32
Unsigned long Output limit value index
R/W
68
32
Unsigned long Output transition vs.
pulse
R/W
72
32
Unsigned long Output pulse type index R/W
R/W
R/W
R/W
76
32
Unsigned long Output pulse ratio (pulses
per kWh/kvarh)
R/W
R/W
R/W
R/W
80
32
Unsigned long DO - Pulse length
R/W
R/W
R/W
R/W
84
32
Unsigned long Dialog language
R/W
R/W
R/W
R/W
88
32
Unsigned long Phase labels (EU/US)
R/W
R/W
R/W
R/W
92
32
Unsigned long Configurable counter
source
R/W
R/W
R/W
R/W
96
32
Unsigned long Display contrast
R/W
R/W
R/W
100
32
Unsigned long Display backlight level
(normal mode)
R/W
R/W
R/W
104
32
Unsigned long Display backlight level
(dimmed mode)
R/W
R/W
R/W
108
32
Unsigned long Time until dimmed
R/W
R/W
R/W
112
32
Unsigned long Digital output timeout
R/W
R/W
R/W
R/W
Summary of Contents for SENTRON PROFINET Proxy SPP2000
Page 1: ......
Page 2: ......
Page 12: ......
Page 34: ......
Page 81: ...PROFINET Proxy SPP2000 Equipment Manual 03 2022 L1V30814715D 01 79 Dimensional drawings 10 ...
Page 82: ......
Page 89: ...PROFINET Proxy SPP2000 Equipment Manual 03 2022 L1V30814715D 01 87 ...
Page 90: ......