Commissioning
6.4 Modbus address register for devices with Modbus interface
7KT multimeter
Manual, 08/2018, 2514284149-01
57
Bit
Measured variable
14
Current transformer 2 on phase L3
15
Current transformer 3 on phase L1
16
Current transformer 3 on phase L2
6.4.3
Setup parameters
Note
You can find further details, such as default values and units, in chapter Parameter tables
(Page 28).
Note
For use with function codes 04 and 06.
M01 General
CODE
MENU
MIN
MAX
DEF
WORDS
ADDRESS
P01.01
Primary current of the
current transformer
1
10000
5
1
5000H
P01.02
Secondary current of the
current transformer
0
1
1
1
5002H
P01.03
Nominal voltage
49
500000
49
2
5004H
P01.04
Rated power
0
1
0
1
5006H
P01.05
Primary rated power
50
500000
100
2
5008H
P01.06
Secondary rated power
50
500
100
1
500AH
P01.07
Wiring configuration
0
5
0
1
500CH
M02 Utility
CODE
MENU
MIN
MAX
DEF
WORDS
ADDRESS
P02.01
Language
0
4
0
1
5080H
P02.03
High backlight level
10
100
100
1
5084H
P02.04
Low backlight level
10
100
30
1
5086H
P02.05
Low backlight delay
5
600
30
1
5088H
P02.06
Default page return
9
600
60
1
508AH
P02.07
Default page
1
32
1
1
508CH
P02.08
Default subpage
0
13
0
1
508EH
P02.09
Display update time
1
50
5
1
5090H
Summary of Contents for SENTRON 7KT PAC1600 Series