Description
3.4 Parameterization
7KT multimeter
32
Manual, 08/2018, 2514284149-01
M04 Integration
Unit
Default
Range
P04.01
Demand values
–
Shift
•
Fixed
•
Shift
•
Bus (7KT1682)
P04.02
Power demand values
min
15
1 … 60
P04.03
Current demand values
P04.04
Voltage demand values
1
P04.05
Frequency demand values
P04.01
Selection of calculation mode
•
Fixed: The instantaneous measurements are integrated for the set time.
Every time this set time elapses, the integrated measurement is updated
with the result of the most recent integration.
•
Shift: The instantaneous measurements are integrated for a time = 1/15 of
the set time. Every time this interval elapses, the oldest value is replaced
by the newly calculated value and the integrated measurement is updated.
A time shift window with the 15 most recent calculated values which
correspond to the set time is taken into account here.
•
Bus: As a fixed mode; however, the integration intervals are defined by
means of synchronization messages sent on the serial bus.
P04.02
Demand value for active, reactive and apparent power
P04.03
Current integration time
P04.04
Voltage integration time
P04.05
Frequency integration time
M05 Hour counter
Unit
Default
Range
P05.01
Activate total hour counter
–
ON
•
OFF
•
ON
P05.02
Activate partial hour counter
•
OFF
•
ON
•
LIMx
P05.03
Channel number (n)
1
1 … 4
Summary of Contents for SENTRON 7KT PAC1600 Series
Page 2: ......
Page 10: ......
Page 14: ......
Page 42: ...Installation removal 4 3 Removal 7KT multimeter 40 Manual 08 2018 2514284149 01 4 3 Removal ...
Page 62: ......
Page 69: ...7KT multimeter Manual 08 2018 2514284149 01 67 Dimensional drawings 9 ...
Page 70: ......
Page 75: ......
Page 76: ......