Accessories
4.3 Connection system
3VA molded case circuit breakers with UL and IEC certification
Manual, 01/2019, L1V30435333-01
205
Terminal cover, extended terminal cover, and offset terminal cover
Note
The offset terminal cover is only available for the 3VA63 and 3VA64 molded case circuit
breakers.
All terminal covers provide IP40 protection at the front of the breaker and IP20 protection at
the infeed and load ends provided that they are correctly installed (cutting of grille structure).
The requirements of NFPA 79 "Protection against electric shock" for UL applications are met
with IP20 protection.
All terminal covers have a marking on the inside face which can be drilled through before the
cover is installed. A voltage detector can be inserted through this hole to test for safe
isolation.
WARNING
Reduced degree of barrier protection
IP40 is not maintained at the front of the breaker if a hole is drilled through the terminal
cover.
Suitable precautions must be taken to safeguard against any hazards posed by this loss of
protection.
①
Marking for holes
Phase barriers can also be installed on all terminal covers to increase clearances and
creepage distances which might be impacted by ionized gas following a short circuit.