Accessories
8.6 Auxiliary switches and auxiliary switch modules
3KC0 manual transfer switching equipment
Manual, 09/2018, L1V30368969105-01
69
Mounting positions and switching behavior
●
Auxiliary switches mounted at position 1 or at contact number 1 or 5 function as leading
switch-off auxiliary switches.
●
Auxiliary switches which are mounted at position 2 or at contact numbers 2 / 6, 3 / 7 and
4 / 8 (position 4 / 8 only with sizes 4 and 5) operate simultaneously with the main switch.
Size 3