Connection
6.2 Connecting to the circuit
3KC0 manual transfer switching equipment
Manual, 09/2018, L1V30368969105-01
47
2.
Position the first cable lug or first busbar at the connecting terminal.
3.
Insert the first bolt from the center through the connecting terminal, the bridging bar and
the cable lug or busbar.
4.
Fix the first half of the bridging bar to the connecting terminal using the nut and washer.
5.
Position the second cable lug or the second busbar at the second connecting terminal
and insert the second bolt from the center through the connecting terminal, the bridging
bar and the cable lug.
6.
Fix the second half of the bridging bar to the connecting terminal using the nut and
washer.
Note
The two halves of the bridging bar must come into contact completely after this work step.
7.
Ensure that both parts of the bridging bar are lying flush.
8.
Insert the bolt from the center through the two halves of the bridging bar and fasten the
two halves with a washer and a nut.