Technical data
10.2 Technical specifications of 3KC0 from 200 to 500 A
3KC0 manual transfer switching equipment
120
Manual, 09/2018, L1V30368969105-01
10.2
Technical specifications of 3KC0 from 200 to 500 A
General technical details
Manual transfer switching equipment (MTSE)
from 200 to 500 A, 3KC0....
36-.P
38-.P
40-.P
42-.P
44-.Q
Size
3
4
Continuous current
A
200
250
315
400
500
Operational voltage at
50/60 Hz AC
in compliance with IEC 60947-6-1
V
415
Operational voltage at
50/60 Hz AC
in compliance with IEC 60947-3
V
690
Insulation voltage (U
i
)
V
1000 AC
Impulse withstand voltage (U
imp
)
kV
12
Overvoltage category with
pollution degree 3
IV
Operational current
in compliance with IEC 60947-6-1
•
AC-31 B, at 415 V
•
AC-32 B, at 415 V
•
AC-33 B, at 415 V
•
AC-35 B, at 400 V
A
A
A
A
200
200
200
200
250
250
250
250
315
315
315
315
400
350
315
350
500
500
500
500
Operational current
in compliance with IEC 60947-3
•
AC-21 A, at AC-22 A, at
415 … 690 V
•
AC-23 A, at 415 V
•
AC-23 A, at 500 V
•
AC-23 A, at 690 V
A
A
A
A
200
200
200
200
250
250
250
250
315
315
315
315
400
400
350
315
500
500
500
500
Operational power
in compliance with IEC 60947-3
•
AC-23 A, at 415 V
•
AC-23 A, at 500 V
•
AC-23 A, at 690 V
kW
kW
kW
110
132
185
132
160
220
160
220
280
220
250
355
280
355
500