Technical specifications
Permitted cable lengths (Industrial
Ethernet)
Alternative combinations per length range
0 to 55 m
• Max. 55 m IE TP Torsion Cable 4x2 with IE FC RJ45 Plug 180 4x2
• Max. 45 m IE TP Torsion Cable 4x2 with IE FC RJ45 + 10 m TP Cord 4x2 via
IE FC RJ45 Outlet
0 to 85 m
• Max. 85 m IE FC TP Marine/Trailing Cable 4x2 with IE FC RJ45 Plug 180 4x2
• Max. 75 m IE FC TP Marine/Trailing Cable 4x2 + 10 m TP Cord 4x2 via IE FC RJ45 Out‐
let
0 to 100 m
• Max. 100 m IE FC TP Standard Cable 4x2 with IE FC RJ45 Plug 180 4x2
• Max. 90 m IE FC TP Standard Cable 4x2 + 10 m TP Cord 4x2 via IE FC RJ45 Outlet
Optical parameters
Cable type
Single mode glass FO cable
Cable cross-section
9/125 μm
Permitted cable length
0 to 10,000 m
Attenuation
≤ 0.5 dB/km at 1310 nm
13 dB max. permitted FO cable attenuation with
2 dB link power margin
Electrical data
Power supply
Rated voltage
24 V DC
Voltage range
19.2 to 28.8 V DC Safe Extra Low Voltage
(SELV)
Design
3-terminal plug-in block
Current consumption
Typical
650 mA
Power loss at 24 V DC
Typical
15.6 W
Overvoltage category
CAT II
Overvoltage protection at input
PTC resettable fuse (1.0 A / 60 V)
Permitted ambient conditions
Ambient temperature
During operation
-10 ℃ to +60 ℃
During storage
-40 ℃ to +80 ℃
During transportation
-40 ℃ to +80 ℃
Relative humidity
During operation
≤ 95% without condensation
Operating altitude
During operation
≤ 2,000 m above sea level at max. +60 °C
ambient temperature
< 3,000 m above sea level at max. +55 °C
ambient temperature
< 4,000 m above sea level at max. +50 °C
ambient temperature
Design, dimensions and weight
Immunity
EN 61000-6-2
Emission
EN 61000-6-4
Degree of protection
IP20
MTBF (EN/IEC 61709; 40 °C)
146 years
Housing material
Polycarbonate (plastic)
Technical specifications
8.8 SCALANCE XB004-1LDG
SCALANCE XB-000
Operating Instructions, 01/2022, A2B00077300-11
77