93/118
Siemens
Heating and D.h.w. Controller RVL481
CE1P2541en
Building Technologies
26 Function block "D.h.w. solar charging"
20.05.2008
T
ON
OFF
TSp
t
TKol
254
1D
14
SD
OFF
SD
ON
TLmin
TKol Collector
temperature
ON/OFF Collector
pump
SD
ON
Temperature differential ON
SD
OFF
Temperature differential OFF
TSp
Storage tank temperature
TLmin Minimum
charging
temperature
T Temperature
t Time
•
The storage tank is charged if the collector temperature exceeds the current storage
temperature by the switch-on differential:
TKol > TSp + SD
ON
•
Storage tank charging is stopped if the collector temperature drops below the tempera-
ture differential:
TKol < TSp + SD
OFF
26.2.2 Minimum
charging
temperature
The collector pump is commissioned only if the collector has a minimum temperature of
30 °C and the required temperature differential is reached.
T
ON
OFF
TLmin 30 °C
SD
ON
- SD
OFF
t
TKol
254
1D
06
TKol Collector
temperature
ON/OFF Collector
pump
SD
ON
Temperature differential ON
SD
OFF
Temperature differential OFF
TLmin Minimum
charging
temperature
T Temperature
t Time
•
Charging is stopped (even if the switch-on differential is reached) if the collector tem-
perature is below the charging temperature:
TKol < TLmin
•
Charging takes place if the collector temperature exceeds the minimum charging tem-
perature (and if the required switch-on differential is reached) by the switch-on differen-
tial (SD
ON
– SD
OFF
):
TKol > TLmin + (SD
ON
– SD
OFF
)