Settings
Settings on the "Enduser level”
Press
or
thus activating the "Enduser" level.
Line
Function, display
Factory setting
(Range)
Setting
Explanations, notes and tips
1
Setpoint for
NORMAL heating
20.0 °C
(0…35)
...................
°C
2 Setpoint
for
REDUCED heating
14.0 °C
(0…35)
...................
°C
3
Setpoint for holi-
days mode / frost
protection
10.0 °C
(0…35)
...................
°C
4
Weekday (for heat-
ing program)
1-7
(1…7)
.........................
1 = Monday
2 = Tuesday
1-7 = all days
5
1st heating period,
start of NORMAL
heating
06:00
(00:00…24:00)
.........................
6
1st heating period,
start of REDUCED
heating
22:00
(00:00…24:00)
.........................
7
2nd heating period,
start of NORMAL
heating
--:--
(00:00…24:00)
.........................
8
2nd heating period,
start of REDUCED
heating
--:--
(00:00…24:00)
.........................
9
3rd heating period,
start of NORMAL
heating
--:--
(00:00…24:00)
.........................
10 3rd heating period,
start of REDUCED
heating
--:--
(00:00…24:00)
.........................
Switching program for heating
circuit
--:-- = period inactive