165 Flow temperature
setpoint
Display function
Current setpoint according to
the composite outside tempera-
ture, heating curve, setting knob
position and setting on operat-
ing line 72
166 Resulting heating
curve
Display function
Resulting setpoint incl. position
of setting knob and setting on
line 72
Left
: Flow setpoint at 15 °C
outside temperature
Right
: Flow setpoint at –5 °C
outside temperature
167 Outside
tempera-
ture for frost protec-
tion for the plant
2.0 °C
(--.- / 0…25)
...................
°C
Setting --- = function disabled
168 Flow
temperature
setpoint for frost
protection for the
plant
15 °C
(0…140)
...................
°C
169 Device
number
0
(0…16)
.........................
170 Segment
number
0
(0…14)
.........................
Bus
address
For addressing the
partner unit, refer to
subsection “Com-
missioning and
functional check”
171 Flow
alarm
--:-- h
(--:-- / 1:00…10:00)
......................
h
Period of time during which the
flow temperature (sensor at
terminal B1) may lie outside the
limits
Setting --:-- = function disabled
0 =
PROTECTION
1 =
AUTO
2 =
REDUCED
172 Operating
mode
when linking termi-
nals H1–M
0
(0…3)
.........................
3 =
NORMAL
173 Amplification
of
locking signal
100 %
(0…200)
....................
%
Response to locking signals