Chapter 6
Certification
RUGGEDCOM RSG2100
Installation Guide
44
EMC and Environmental Type Tests
Test
Description
Test Levels
Severity Levels
1000 A/m for 1 s
IEC 61000-4-11
Voltage Dips
and Interrupts
AC Power Ports
30% for 1 period
60% for 50 periods
100% for 5 periods
100% for 50 periods
Signal Ports
DC Power Ports
IEC 61000-4-12
Damped Oscillatory
AC Power Ports
2.5 kV Common
1 kV Differential
Mode @1 MHz
3
Signal Ports
IEC 61000-4-16
Mains Frequency Voltage
AC and DC Power Ports
30 V Continuous
300 V for 1s
4
IEC 61000-4-17
Ripple on DC
Power Supply
DC Power Ports
10%
3
IEC 61000-4-18
Damped Oscillatory Wave
Slow Damped
2.5 kV Common Mode
on Power and Signal
1.0 kV Differential
Mode on Power
3
IEC 61000-4-29
Voltage Dips
and Interrupts
DC Power Ports
30% for 0.1 s
60% for 0.1 s
100% for 0.05 s
Signal Ports
2 kV (Fail-Safe
Relay Output)
DC Power Ports
2 kV
Dielectric Strength
AC Power Ports
2 kV
Signal Ports
5 kV (Fail-Safe
Relay Output)
DC Power Ports
IEC 60255-5
HV Impulse
AC Power Ports
5 kV
a
Siemens-specified severity levels
EMC Immunity Type Tests per IEEE 1613
NOTE
The RUGGEDCOM RSG2100 meets Class 2 requirements for an all-fiber configuration and Class 1
requirements for copper ports. Class 1 allows for temporary communication loss, while Class 2 requires
error-free and interrupted communications.
Description
Test Levels
Enclosure Contact
±2 kV
±4 kV
±8 kV
ESD
Enclosure Air
±4 kV
Summary of Contents for RUGGEDCOM RSG2100
Page 4: ...RUGGEDCOM RSG2100 Installation Guide iv ...
Page 12: ...Chapter 1 Introduction RUGGEDCOM RSG2100 Installation Guide 4 Description ...
Page 28: ...Chapter 2 Installing Device RUGGEDCOM RSG2100 Installation Guide 20 Configuring the Device ...
Page 46: ...Chapter 5 Dimension Drawings RUGGEDCOM RSG2100 Installation Guide 38 ...