RUGGEDCOM RSG2100
Installation Guide
Chapter 6
Certification
EMC and Environmental Type Tests
43
•
IEC 61850-3
Communication Networks and Systems in Substations – Part 3: General Requirements
•
EN 50121-4
Railway Applications – Electromagnetic Compatibility – Emission and Immunity of the Signaling and
Telecommunications Apparatus
Section 6.2
EMC and Environmental Type Tests
The RUGGEDCOM RSG2100 has passed the following Electromagnetic Compatibility (EMC) and environmental
tests.
EMC Type Tests per IEC 61850-3
NOTE
• In the case of an all fiber port configuration, this product meets all Class 2 requirements. Otherwise,
all Class 1 requirements are met for copper ports.
• If the unit contains copper ports, the IEC 1613 conformance is Class 1, during which disturbance
errors may occur but recovery is automatic.
• If the unit contains all fiber ports, the IEC 1613 conformance is Class 2, during which no disturbance
errors will occur.
Test
Description
Test Levels
Severity Levels
Enclosure Contact
±8 kV
IEC 61000-4-2
ESD
Enclosure Air
±15 kV
4
IEC 61000-4-3
Radiated RFI
Enclosure Ports
20 V/m
Note
a
Signal Ports
±4 kV @ 2.5 kHz
Note
a
DC Power Ports
AC Power Ports
IEC 61000-4-4
Burst (Fast Transient)
Earth Ground Ports
±4 kV
4
Signal Ports
±4 kV Line-to-Ground,
±2 kV Line-to-Line
4
DC Power Ports
±2 kV Line-to-Ground,
±1 kV Line-to-Line
3
IEC 61000-4-5
Surge
AC Power Ports
±4 kV Line-to-Ground,
±2 kV Line-to-Line
4
Signal Ports
DC Power Ports
AC Power Ports
IEC 61000-4-6
Induced (Conducted) RFI
Earth Ground Ports
10 V
3
IEC 61000-4-8
Magnetic Field
Enclosure Ports
100 A/m Continuous
5
Summary of Contents for RUGGEDCOM RSG2100
Page 4: ...RUGGEDCOM RSG2100 Installation Guide iv ...
Page 12: ...Chapter 1 Introduction RUGGEDCOM RSG2100 Installation Guide 4 Description ...
Page 28: ...Chapter 2 Installing Device RUGGEDCOM RSG2100 Installation Guide 20 Configuring the Device ...
Page 46: ...Chapter 5 Dimension Drawings RUGGEDCOM RSG2100 Installation Guide 38 ...