Page 22
Pointek CLS 300 – INSTRUCTION MANUAL
7ML19985CK03
Case 1
Preparation
•
Ensure that L3 (green) is
ON
•
Turn both potentiometers,
P1
and
P2
, fully CCW (counter-clockwise)
•
Set
S1
switches
1
to
4
to
OFF
and S1 switch 5 to
ON
(normal sensitivity)
Configuration
1.
With sensor uncovered and a minimum 100mm free space all around, turn
P2
CW until
L1 (yellow) goes
ON
.
2.
Turn P2 CCW until L1 goes
OFF
.
Case 2
Preparation
•
Ensure that L3 (green) is
ON
•
Turn potentiometer P1 fully CCW (counter-clockwise)
•
Turn P2 fully CW (clockwise)
•
Set S1 switches
1
through
5
to
OFF
Configuration
1.
Immerse the sensor in the material that has the lowest dielectric constant. L1 (yellow)
should be
ON
. (If L1 does not light, set S1 switch 5 to
ON
[normal sensitivity].)
2.
Adjust P2 CCW until L1 goes
OFF
.
3.
Immerse the sensor in the material that has the highest dielectric constant; L1 should
come
ON
.
Trip Amplifier