7ML19985CK03
Pointek CLS 300 – INSTRUCTION MANUAL
Page 17
Relay Output Connection
Relay shown in de-energized state.
K2 contact ratings:
•
8A at 250V ac
•
5A at 30V dc
Solid State Switch
Switch shown in de-energized state.
K3 contact ratings:
•
250V ac,100mA, max, non-
polarized (max 2VA)
•
300V dc, 100mA max, non-
polarized (max 2VA)
Diode Protection
When driving an external relay with either the solid stated switch and/or relay outputs using
dc power, protection diodes must be connected in the correct polarity across the relay coil to
prevent possible switch/relay damage resulting from inductive spikes generated by the relay
coil.
Switch capacity:
•
250V ac
100mA max
2VA/2W max
•
300V dc.
100mA max
2VA/2W max
relay coil
Customer supplied diode protection
relay coil
Customer supplied diode protection
Solid-state switch to customer’s control
or instrumentation device