Appendix
A.3 Application examples for functional safety (STO / SS1-t)
Power Module PM330
Hardware Installation Manual, 12/2018, A5E32844552B AF
131
Scenario 2:
●
LED 1 DEVICE is OFF
-> fault
●
LED 2 OUT is OFF
-> the safety circuit is not enabled
Possible causes:
●
3SK1 power supply missing
●
Short or cross-circuit faults at the 3SK1
–
Between the cycle outputs
–
In or to the power supply
–
In the input circuit (sensor circuit)
–
In the enable circuits
–
In the feedback signal circuit
Safety relay 3SK1 Advanced or 3SK1112… being used
Scenario 3:
●
LED 1 DEVICE lights up green
–
-> power supply, power up and configuration are OK
●
LED 2 OUT is OFF
–
-> the safety circuit is not enabled
Possible causes:
●
LED 3 IN is OFF
-> close sensor circuit through 2 channels
●
LED 3 IN flashes green
–
LED 4 SF is OFF -> START button not pressed
–
LED 4 SF flashes red-> simultaneity for 1x2 channel sensor not met
–
LED 4 SF flashes red-> time monitoring for two-handed start violated
●
LED 3 IN flashes yellow
–
LED 4 SF flashes red -> short-circuit T1/T2 with respect to ground or 24 V