Appendix
A.3 Application examples for functional safety (STO / SS1-t)
Power Module PM330
132
Hardware Installation Manual, 12/2018, A5E32844552B AF
Scenario 4:
●
LED 1 DEVICE is OFF
-> group fault
●
LED 2 OUT is OFF
-> the safety circuit is not enabled
●
LED 3 IN flashes yellow
-> group fault, input circuit
●
LED 4 SF is lit red
-> group fault
Possible causes:
●
Group fault, cross-circuit fault in the input circuits
Scenario 5:
●
LED 1 DEVICE is lit green
-> power supply, power up and configuration are OK
●
LED 2 OUT flashes green
-> feedback circuit fault
●
LED 3 IN flashes green
-> feedback circuit fault
●
LED 4 SF flashes red
-> fault
Possible causes:
●
Interruption in the feedback circuit wiring
●
Incorrect feedback circuit wiring
●
PM330 fault
–
PM330 power supply missing -> establish the power supply
–
One or two of the STO inputs of the PM330 has a high signal, e.g. as a result of short
circuit or cross circuit fault in the wiring
–
One or two switch-off signal paths of the PM330 is/are defective
–
One or two feedback signal paths of the PM330 is/are defective