Operating the circuit-breaker panel
62
NXAIR /
≤ 40 kA
110-0134.9 / 14
NOTICE
Conflicting operation
The requirement of setting the panel to either local or remote control prevents
operating the panel locally and centrally at the same time.
For charging the spring energy store manually, set the panel to local
control, for example by switching the local-remote switch to LOCAL
position.
INFORMATION
Rhythmical noises
Turning the hand crank for charging the spring energy store in the circuit-breaker
causes rhythmical noises and low vibration.
Fig. 88: Hand crank not removed
Preconditions
•
Withdrawable circuit-breaker / circuit-breaker truck in service position or in test position
•
Circuit-breaker in OPEN position or CLOSED position
•
Spring state indicator for the closing spring shows DISCHARGED
•
High-voltage door closed
•
Auxiliary voltage for the panel disconnected
•
Hand crank available
Fig. 89: Actuating opening on
high-voltage door
Fig. 90: Hand crank for manual charging of the
spring energy store in the circuit-breaker